Sensors permissible values
Any contact closure or pulse sensor (digital) or two wire analogue sensors may
be connected to the Flexi Logger 300Ex provided the sensor meets the following
criteria:
•
The sensor must have ATEX or IECEx certification for use in the
hazardous zone they are being used in.
•
The sensors output parameters are not greater than the maximum
permissible values detailed below:
Parameter
Sensor connector
permissible values
Voltage Out - Uo
22.7v
Current Out - Io
297mA at 14.6v*
Power Out - Po
1.1W *
Capacitance - Ci
0.2uF
Inductance - Li
1.61mH
*Combined total for all three connectors