TransformerCare Unit
TCU in operation
HYDAC FILTER SYSTEMS GMBH
en
Page 34 / 64
BeWa TCU 3472805b en 2011-07-05.doc
2011-07-05
TCU in operation
Start / Stop
Use the main switch (17) on the switch box to switch the TCU on or off.
Every time the TCU restarts, the time delay (K1) will begin a new countdown. Within
the delay time, the alarm's functions like, for example, stopping pressure (SP1) or
the safety switch (14) in the safety drip tray are deactivated.
Monitor the system until the indicator lamp goes out (~ 5 minutes).
Settings
Setting the time relay (K1)
To adjust the time relay, proceed as follows:
1.
Switch off the TCU at the main switch (17) and disconnect the TCU from the
power supply.
2.
Open the electrical switch box.
3.
Use a suitable screwdriver to turn the adjusting wheel on the time relay (K1)
to the required time (~ 5 minutes).
4.
Close the cover of the electrical switch box and connect the electrical power
supply again.