Damocles2
Ares LTE
33
Customizing user messages
Format and datalog description
Ares LTE supports up to 4 user-defined custom types of e-mail and text messages. The following
macro commands can be used to insert system variables, sensor names and measured values.
List of macro commands
Detailed description of XML and datalog formats can be found in AN51 on HW group website.
Name
Description
General
General macros
%DEV_NAME%
Device name
%MSG_TYPE%
Message type (alarm, status, periodic)
Source sensor
%SRC_TYPE%
Sensor name
%SRC_VALUE%
Current value
%SRC_UNIT%
Unit of the measured value
%SRC_STATUS%
Sensors: Invalid, Normal, Alarm, Out Of Range
Digital inputs: Normal, Alarm
%SRC_MIN%
Lower limit of the Safe Range
%SRC_MAX%
Upper limit of the Safe Range
%SRC_ALARM%
Alarm begin/end
Sensor with ID=XXXX
Information about other sensors to include in the message
%NAME_XXXX%
XXXX sensor name
%VALUE_XXXX%
XXXX sensor reading
%UNIT_XXXX%
XXXX sensor unit of measurement
%STATUS_XXXX%
Sensors: Invalid, Normal, Alarm, Out Of Range
Digital inputs: Normal, Alarm
%MIN_XXXX%
Lower limit of the Safe Range XXXX
%MAX_XXXX%
Upper limit of the Safe Range XXXX
%ALARM_XXXX%
Alarm begin/end
SMS
%TABLE SENSORS%
Chart of status and values of individual sensors
%TABLE INPUTS%
Chart of status and values of individual inputs
Customizing user messages / Format and datalog description
Содержание Ares 10 LTE
Страница 1: ...Ares 10 12 LTE User manual...