REFRIGERANT
The correct type of refrigerant will be stamped on
each merchandiser’s serial plate. The case refrig-
eration piping is factory sealed, pressurized and
leak tested. Before making refrigeration hookups,
depress universal line valve to ensure that coils
have maintained pressure during shipment.
REFRIGERANT PIPING
Connection Location
The refrigerant line connections are at the right-
hand end of the merchandiser (as viewed from the
front) beneath the display pans. A sticker marks
the location of the connection “pod.” The installer
must saw a hole through the pod to exit the case.
After connections have been made, seal this outlet
thoroughly. Seal both the inside and the outside.
We recommend using an expanding polyurethane
foam insulation.
Multiplexing
Piping of merchandisers operating on the same
refrigeration system may be run from merchan-
diser to merchandiser. D
O NOT RUN REFRIGERANT
LINES THROUGH MERCHANDISERS THAT ARE NOT
ON THE SAME REFRIGERATION SYSTEM BRANCH
as
this may result in poor refrigeration control and
compressor failure.
Interconnecting piping inside the merchandiser
must be located as shown below to allow room for
lifting the hinged fan plenums and for clearance
beneath the display pans. The interconnecting
piping may be run outside the case.
Line Sizing
Refrigerant lines should be sized as shown on the
refrigeration legend that is furnished for the store
or according to ASHRAE guidelines. Refer to the
information on the next page for branch line
piping of Hussmann Equipment.
Oil Traps
P-traps (oil traps) must be installed at the base of
all suction line vertical risers.
Pressure Drop
Pressure drop can rob the system of capacity. To
keep the pressure drop to a minimum, keep the
refrigerant line run as short as possible using a
minimum number of elbows. Where elbows are
required,
USE LONG RADIUS ELBOWS ONLY
.
P/N 406928
2-1
E
Eu
urro
o D
De
ellii M
Me
errc
ch
ha
an
nd
diisse
errss
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)
R
RE
EF
FR
RIIG
GE
ER
RA
AT
TIIO
ON
N // E
EL
LE
EC
CT
TR
RIIC
CA
AL
L
Refrigeration lines are under pressure
and should be depressurized before
attempting to make any connections.
WARNING
!
Piping Location
Display Pan
Fan
Coil
When brazing pipes be sure to use the
insulation blanket shipped with the
merchandiser to prevent damage to the
plastic case bottom.
CAUTION
!