3-2

 

D

RIP

 P

IPIng

 

anD

 s

PlashguaRDs

P/N 3093114_A

U.S. & Canada 1-800-922-1919 • Mexico 1-800-522-1900 • WWW.HUSSMANN.COM

INSTALLING DRIP PIPING

Poorly or improperly installed drip pipes can  
seriously interfere with the merchandiser’s 
operation and result in costly maintenance and 
product losses. 

Optional drip pipe arrangements are shown on 
the next page. Assemble the components using 
PVC specific threaded pipe sealer according to 
the manufacturer’s direction.

Please follow the recommendations listed 
below when installing drip pipes to ensure 
proper installation.

1.  Never use drip piping smaller than the 

nominal diameter of the pipe or water seal 
supplied with the merchandiser.

2.  When connecting drip piping, the 

water 

seal

 must be used as part of the drip piping 

to prevent air leakage or insect entrance. 
Never use two water seals in series in any 
one drip pipe. 

d

ouble

 

waTer

 

seals

 

in

 

series

 

will

 

cause

 

an

 

air

 

lock

 

and

  

prevenT

 

draining

.

3.  Pitch the drip piping in the direction of 

flow. 

There should be a minimum pitch of 

1

/

4

 in. per ft (20 mm per 1 m).

4.  Avoid long runs of drip piping. Long runs 

make it impossible to provide the pitch  
necessary for good drainage.

5.  Ensure that drip piping is supported to 

relieve any stress on drip pipe connectors 
and drain hub. 

 

a. Drip piping 

MUST

 be supported 24 inches  

from drain hub tee.

6.  Provide a suitable air break 
between flood rim of the floor drain 
and outlet of drip pipe. To meet code 
requirements, it may be necessary 
to install a field-supplied drip pipe 
reducer. An alternative is to cut the 
last section of drip pipe at an angle.

7.  Prevent drip pipes from freezing:

 

a.  Do NOT install drip pipes in contact    

 

with uninsulated suction lines. Suction lines 

 

should be installed with a nonabsorbent    

 

insulation material.

 

b.  Where drip pipes are located in dead air  

 

spaces, such as between merchandisers or   

 

between a merchandiser and a store wall,   

 

provide means to prevent freezing.

It is the installing contractor’s 

responsibility to consult local agencies 

for local code requirements. 

Содержание BEXDW8G

Страница 1: ...e Deck Merchandisers Installation Operation Manual Shipped with Merchandiser Data Sheets P N 3093114_A Excel Series April 2019 IMPORTANT Keep in store for future reference MANUAL I O BEXDWG Spanish 30...

Страница 2: ...ified by the California State government Proposition 65 can be considered more of a right to know law than a pure product safety law When used as designed Hussmann believes that our products are not h...

Страница 3: ...Defrost 2 3 Liquid Line Off time and Electric Defrost 2 4 Liquid Line Koolgas Defrost 2 4 Front to Rear and or End Interconnects 2 4 Refrigeration Thermostat 2 4 Defrost Termination Thermostat 2 4 CDA...

Страница 4: ...4 ft suggested Ratchet in Socket 5 16 in Socket in Socket Battery Drill Screw Gun Caulking Gun 10 in Adjustable Crescent Wrench REVISION HISTORY REVISION A ORIGINAL ISSUE APRIL 2019 Merchandiser must...

Страница 5: ...ir currents passing around merchandisers will seriously impair their operation Do NOT allow air conditioning electric fans open doors or windows etc to create air currents around the merchandisers Pro...

Страница 6: ...l electrical and refrigeration connections will be made at the front side the fronts will need to be positioned according to the store plan layout A secondary serial number sticker is put on the exter...

Страница 7: ...r or merchandiser lineup to prevent condensation 2 Snap a chalk line for the front and rear positions of the base legs 3 Mark the location of each joint from front to back lines 4 FLOORS ARE NOT LEVEL...

Страница 8: ...he first merchandiser at the highest point Set a long level 4 ft 1220 mm or more on top of the discharge air flue Insert shims until the merchandiser is level from end to end and from front to back NO...

Страница 9: ...G MERCHANDISERS IN LINE 1 Remove and retain any factory installed fasteners 2 Move merchandisers in lineup as close as possible by pushing or using lever bar mule 3 Verify upper front panel front pane...

Страница 10: ...op rail Shim cases to ensure vertical alignment of panels and top rails 4 Align frame fasteners Fastener size and location are detailed on Pages 1 8 and 1 9 Loosely assemble bolt washers lock washer a...

Страница 11: ...in bumper retainers Joining brackets are installed in factory Be sure to loosen joining bracket screws before tightening and joining the bumper brackets Tighten the screws of joining brackets after ti...

Страница 12: ...WW HUSSMANN COM Parent to Parent Installation Loosely fasten 5 16 18 X 1 3 4 in Hex Head Screw from provided case packout kit as shown in locations circled in the image below Use a socket with a U joi...

Страница 13: ...83 U S A Fasten End Frames 1 Tighten joints in the order shown until gaskets are compressed and merchandisers join smoothly Work from the lower front to lower back to upper back Fasten the upper front...

Страница 14: ...e merchandiser and level to the floor Each bracket has a 11 2 in 38 mm slot at the rear of the bracket where it attaches to the merchandiser Tighten screws to secure the brackets Important Install spl...

Страница 15: ...gh bumpers can usually be removed by hand a simple tool to remove bumpers can be created by wrapping tape over the claw of a small pry bar as shown here The pry bar is available at most local hardware...

Страница 16: ...tall full length bumpers and internal trims offset across joints Make sure that no gaps exist between sections Continue installing the bumpers the length of the lineup 4 Once all except the last secti...

Страница 17: ...tall offsetting bumpers a Remove bumpers from cooler Measure bumpers and cut to appropriate length Use a miter box and fine tooth saw b Insert internal joint trims first Install bumpers offset across...

Страница 18: ...chandiser is fastened b Tighten in order shown for joining 4 Seal End to End Frame Remove front shelf and shelf support bracket Apply a 1 2 in bead of Silicone at the back of the case starting at the...

Страница 19: ...hen the shroud is rotated into place it will be in the upright position The Figure 2 1 shows the correct orientation Be careful not to burn scorch or overheat the shroud when making connections Once c...

Страница 20: ...rol and compressor failure Interconnecting piping inside the merchandiser must be located as shown below for clearance beneath the display pans Alternately the interconnecting piping may be run outsid...

Страница 21: ...ith EITHER of Above Additional insulation for the balance of the liquid and suction lines is recommended wher ever condensation drippage is objectionable or the lines are exposed to ambient conditions...

Страница 22: ...8 1 3 8 1 1 8 1 5 8 1 3 8 2 1 8 Take offs to evaporators exit the bottom of the liquid line Provide an expansion loop for each evaporator take off minimum 3 in 76 mm diameter REFRIGERATION THERMOSTAT...

Страница 23: ...des All electrical connections are to be made in the electrical wireway or Handy Box IDENTIFICATION OF WIRING Leads for all electrical circuits are identified by colored plastic bands These bands corr...

Страница 24: ...2 6 Installation P N 3093114_A U S Canada 1 800 922 1919 Mexico 1 800 890 2900 WWW HUSSMANN COM NOTES...

Страница 25: ...ith clean outs or elbows are supplied for each merchandiser One water seal is sup plied for each merchandiser The water seal must be installed with the waste outlets to prevent air leakage and insect...

Страница 26: ...r lock and prevent draining 3 Pitch the drip piping in the direction of flow There should be a minimum pitch of 1 4 in per ft 20 mm per 1 m 4 Avoid long runs of drip piping Long runs make it impossibl...

Страница 27: ...ons are for reference only Piping may vary with location and access to hub drain s Each merchandiser waste outlet must be individually piped to a hub drain if 1 4 in drip piping pitch cannot be mainta...

Страница 28: ...the next page To Install Splashguards 1 Check to be sure that all splashguard brackets are level with the floor 2 Position top of splashguard with the top angled in as shown in the illustration Align...

Страница 29: ...re a secure installation 2 Apply a good contact cement to the cove trim and allow proper drying time according to the directions supplied with the cement 3 Install the trim to the splashguard so that...

Страница 30: ...fter main splashguards 1 Check to be sure that all splashguard brackets are level with the floor 2 Position top of splashguard with the top angled in behind the lower panel bracket 3 Raise the splashg...

Страница 31: ...these grilles Do not use non approved shelving baskets display racks or any accessory that could hamper air curtain performance LOAD LIMITS Each merchandiser has a load limit decal Shelf life of peris...

Страница 32: ...ANN COM This is an NSF 7 US FDA Food Code Required Thermometer Hussmann P N 0429971_C 10 2007 Hussmann Corporation 12999 St Charles Rock Road Bridgeton MO 63044 2483 U S Canada 1 800 922 1919 Mexico 1...

Страница 33: ...mometer may need to be moved several times to find the warmest location Mounting options include flexible plastic for price tag molding application magnet applied to back of flexible plastic for steel...

Страница 34: ...4 4 Start up Operation P N 3093114_A U S Canada 1 800 922 1919 Mexico 1 800 890 2900 WWW HUSSMANN COM NOTES...

Страница 35: ...ing the waste outlet Store product in a refrigerated area such as a freezer Remove only as much product as can be taken to the freezer in a timely manner First turn off refrigeration then disconnect e...

Страница 36: ...emove clips from panel Lift out return air grilles The glass may be cleaned with most domestic detergents ammo nia based cleaners and sanitizing solutions with no harm to the surface Never use abra si...

Страница 37: ...ins Contact an authorized service technician if a coil is punctured cracked or otherwise damaged ICE in or on the coil indicates the refrigera tion and defrost cycle is not operating prop erly Contact...

Страница 38: ...using the following procedure 1 Use steel wool to smooth out the surface area of the bumper or top rail 2 Clean area 3 Apply vinyl or car wax and polish surface for a smooth glossy finish CLEANING UN...

Страница 39: ...plenum and remove assembly 6 Replace fan motor bracket assembly and reinstall screws 7 Reinstall fan blade 8 Reconnect fan to wiring harness 9 Turn on power 10 Verify that motor is working and blade i...

Страница 40: ...to jumper harness plug in LOCK OUT TAG OUT To avoid serious injury or death from electri cal shock always disconnect the electrical power at the main disconnect when servicing or replacing any electr...

Страница 41: ...h as a putty knife to separate the guard from the panel until a finger can be inserted to rotate the guard off the panel Work the length of the panel To reinstall hook the curved leg of the edge guard...

Страница 42: ...414 X Ergon 1570 E Northgate P O Box 2102 Irving TX 75062 Phone 1 800 527 9916 NOTE Hussmann Aluminum melts at 1125 F Aladdin 3 in 1 rod at 732 F X Ergon Acid core at 455 F Technique 1 Locate Leak 2 R...

Страница 43: ...information or other support contact your Hussmann representative Please include the model and serial number of the product Hussmann Corporation Corporate Headquarters Bridgeton Missouri U S A 63044 2...

Страница 44: ...Hussmann Corporation 12999 St Charles Rock Road Bridgeton MO 63044 2483 www hussmann com...

Отзывы: