product manual
07.10
H-3600
Cement Bleeding Apparatus
Страница 1: ...product manual 07 10 H 3600 Cement Bleeding Apparatus ...
Страница 2: ...Procedure 4 1 Pastes Immediately after mixing carefully pour the paste into the sample container and take the completion of the screening as the start time for the test Take care to make certain that the paste height is level with the edge of the 5 diameter container Place the collecting ring approximately in the center of the paste surface embed it to a depth of approximately 1 4 and cover the su...
Страница 3: ...ng bowl for 30 seconds Within a total elapsed time of not more than 2 1 2 minutes after completion of the original mixing of the mortar batch begin placing the mortar in the sample container Place the mortar in three layers tamp each layer 40 times with the tamper and strike off the surface level with the edge of the 5 diameter container by screeding with a steel straight edge Con duct the remaind...
Страница 4: ...tion charges Humboldt Mfg Co shall not be responsible under this warranty if the goods have been improperly maintained installed operated or the goods have been altered or modified so as to adversely affect the operation use performance or durability or so as to change their intended use The Humboldt Mfg Co liability under the warranty contained in this clause is limited to the repair or replaceme...