27
A.FULL
Set Analog Retransmit
Fullscale Value
Press
ENTER/SAVE
Press
INCREASE
DECREASE
Press
ENTER/SAVE
The display will show the current retransmit fullscale value.
Pressing the INCREASE or DECREASE pushbutton will increase or decrease
the retransmit setting. Hold it until the desired value is reached. The longer the
pushbutton is held, the faster the display moves to the required setting.
To save the new retransmit fullscale setting, press the ENTER/SAVE
pushbutton.
This function controls the fullscale value of the analog retransmit signal. It may be set to any
value between 0 and 20 mA (milliAmps) in 0.001 mA increments. Typical values are 1 for a 0
to 1 mA signal and 20 mA for a 4 to 20 mA signal.
S.GRAV
Set Specific Gravity
Correction Factor
Press
ENTER/SAVE
Press
INCREASE
DECREASE
Press
ENTER/SAVE
The display will show the current specific gravity correction factor setting.
Pressing the INCREASE or DECREASE pushbutton will increase or decrease
the specific gravity correction factor setting. The correction factor may be set
from 0 to 2.000 in increments of .001.
Press ENTER/SAVE to store the new setting.
This function allows the entry of a correction factor for specific gravity. The correction factor
may be set from 0 to 2.000 in increments of .001.
This correction factor is a simple multiplier. Any input values are multiplied by this factor
before being displayed.