U-ONE
®
-SAFETY-LWL
Configuration manual
26
USL_KonfigManual-en_R3
5.2 Incremental output
Required modules
USL(H) 42 Basic Device
UO-SCU-G Module
Please see the specific module operating and assembly manuals for further
important information.
The incremental output is optional and is installed in
the UO-SCU-G. A division factor of 1, 2, 4 or 8 can
be selected for the incremental output via the option
menu. The resulting pulse count is displayed directly
(for default setting see section 6.7).
5.3 PROFIBUS-DP interface (UO-EPB-1)
Required modules
USL(H) 42 Basic Device
UO-SCU Module
UO-EPB-1 module
Please see the specific module operating and assembly manuals for further
important information.
The module transmits the Multiturn and Singleturn absolute value for the basic device. It can be
configured in profiles CLASS 1 (Hübner 1.0) with configuration of the counting direction and
CLASS 2 (Hübner 2.0) with the additional setting for resolution / revolution and the overall
resolution.
The profiles Hübner 2.1 and Hübner 2.2 are also available. These also provide the following
functions:
Expanded scaling function
Setting the counting direction, preset and automatic scaling (teach in) during online operation
in commissioning mode.
Limit switch function
Speed output
NOTE!
The UO-EPB-1 can only be configured via the field bus interface.
A preset over the field bus interface does not influence the preset specified
in the UO-SCU. We recommend setting both presets to the same value
when the module is shut down.
Fig. 5-3: Incremental output