Incremental Encoder FG 40

 

 

28 

 

FG40_MANUAL-en_R12(2018-10-31)ID74490.doc 

 

8

 

Inspections 

8.1

 

Safety instructions 

 

WARNING! 

Skilled technical staff only are permitted to inspect the device and its installation. 

Observe the safety instructions contained in Chapter 2 when inspecting or working on 
the device! 

8.2

 

Maintenance information 

The device is maintenance-free. However, to guarantee optimum fault-free operations we recommend 
that you carry out the following inspections. 

8.3

 

Inspection schedule 

Interval 

Inspections 

Yearly 

Inspect the coupling for damage and ensure it is free of play 

Ensure the fastening screws are properly tightened 

Ensure cable connections and connection terminals are 
securely seated 

Following approx 16 000 … 20 000 
hours of operation / higher levels of 
continuous load 

Check deep groove ball bearings are running smoothly and 
listen for running noises 

9

 

Disposal 

9.1

 

Disposal procedure 

The manufacturer is not obliged to take back the device. 

The  device  is  classed  as  electronic  equipment  and  subject  to  the  WEEE  Directive;  observe  local, 
country-specific laws when disposing of the device. 

For  information  on  environmentally  sound  disposal  please  contact  your  local  authority  or  a  specialist 
disposal company. 

10

 

Replacement parts 

The replacement parts listed below can be obtained via the service address on page 2. 

Replacement parts 

Comment 

Cover 

Cover for the 2nd shaft end or for the hollow shaft bore (gAS) 

Cable gland 

M 20 x 1.5 

Terminal box cover 

Including flat seal and screws 

Feather key 

Specify shaft dimensions or feather key dimension 

Programming cable and software 

 

Screw plug 

For closing the access to the coupling 

Содержание FG 40 Series

Страница 1: ...embly Instructions FG40_MANUAL en_R12 2018 10 31 ID74490 doc ID 74490 Operating and Assembly Instructions Incremental Encoder FG 40 Read the Operating and Assembly Instructions prior to assembly starting installation and handling Keep for future reference ...

Страница 2: ...straße 7 35394 Giessen Germany Phone 49 641 7969 0 Fax 49 641 73645 Internet www huebner giessen com E Mail info huebner giessen com The manual has been drawn up with the utmost care and attention Nevertheless we cannot exclude the possibility of errors in form and content It is strictly forbidden to reproduce this publication or parts of this publication in any form or by any means without the pr...

Страница 3: ... 3 Safeguarding against restart 7 3 Technical Data 8 3 1 Type plates 8 3 2 Electrical and mechanical data 9 3 2 1 For pulse rates square wave pulses 9 3 2 2 Output signals Sine Cosine 10 3 3 Type code 14 3 3 1 For pulse rates square wave pulses 14 3 3 2 For output signals Sine Cosine 15 4 Transport packaging and storage 16 4 1 Safety instructions for transport 16 4 2 Incoming goods inspection 16 4...

Страница 4: ... Faults 27 7 1 Faults table 27 8 Inspections 28 8 1 Safety instructions 28 8 2 Maintenance information 28 8 3 Inspection schedule 28 9 Disposal 28 9 1 Disposal procedure 28 10 Replacement parts 28 11 Dimension drawings 29 11 1 Construction type B5 flange 29 11 2 Construction type B35 flange and foot 31 11 3 Construction type B5 B14 flange with 2 shaft ends 33 11 4 construction type B35 B14 flange ...

Страница 5: ... warnings must be strictly heeded you must act prudently to prevent accidents personal injury and property damage WARNING Indicates a possibly dangerous situation that can result in death or serious injury if it is not avoided CAUTION Indicates a possibly dangerous situation that can result in minor injury if it is not avoided CAUTION Indicates a possibly dangerous situation that can result in mat...

Страница 6: ...s will be prosecuted 1 6 Guarantee terms The guarantee terms are provided in the manufacturer s terms and conditions 1 7 Customer service For technical information personnel is available that can be contacted by telephone fax or email See manufacturer s address on page 2 2 Safety DANGER This section provides an overview of all the important safety aspects that ensure protection of personnel as wel...

Страница 7: ...k There is an imminent life threatening hazard if live parts are touched Damage to insulation or to specific components can pose a life threatening hazard Therefore Immediately switch off the device and have it repaired if there is damage to the insulation of the power supply De energize the electrical equipment and ensure that all components are connected for all tasks on the electrical equipment...

Страница 8: ...oder with one terminal box Encoder with 2 terminal boxes redundant version Encoder with 2 sinusoidal signals The type plate is located on the outside of the housing and contains the following information Manufacturer Address Type year of construction CE marking Serial number S N Commission number C N Pulse rate Protection class Power supply No load current Outputs ...

Страница 9: ...ed short circuit proof push pull line driver with integrated impedance adaptation for 30 to 140 Ω lines Pulse height HTL approx as supply voltage output saturation voltage 0 4 V at IL 30 mA Output current max 150 mA at 24 V observe derating Internal resistance 75 Ω bei 24 V Slew rate 200 V µs with CL 100 pF Duty cycle 1 1 3 for standard pulse rates 1 1 5 for special pulse rates up to 25000 pulses ...

Страница 10: ... Supply voltage 5 V 30 V DC No load current Approx 120 mA at 5 V approx 50 mA at 24 V Max frequency 200 kHz higher max frequency on request Output signals 2 sinusoidal signals A and B each with inverted signals Reference pulse with inverted signal Signal amplitude 1 V pp RL 120 Ω Error signal and inverted signal Signal amplitude 5V Resolution 1024 signal periodes Duty cycle 1 0 1 Phase shift A B 9...

Страница 11: ... rolling mills 3000 min 1 510 gcm 9 Ncm Encoder temperature ranges Standard 0 C 70 C Special temperature ranges 25 C 85 C 40 C 85 C 5 C 100 C Special output voltage 5V TTL Pulse height 5V RS422 compatible TIA EIA Standard Supply voltage 12 30 V DC optional 5V DC Vibration resistance DIN EN 60068 2 6 IEC 68 2 6 10 2000 Hz 20 g 200 m s Shock resistance DIN EN 60068 2 27 IEC 68 2 27 6 ms 150 g 1500 m...

Страница 12: ...nal standstill recognition Option B3 Rotation dependent output signals This option supports counter cards with separate UP DOWN pulse inputs Basic channel signals are issued at option output 1 when rotation is clockwise and at option output 2 when rotation is counterclockwise Option S Electronic overspeed switch with two independently programmable switching points See separate Operating and Assemb...

Страница 13: ...oc 13 Signal outputs for output signals sine cosine Basic channel 0 A and pulse channel 90 B Reference pulse N mechanically defined one square wave pulse per revolution with inverted signal Each with inverted signal Internal system diagnostics with error output ERROR ...

Страница 14: ...plug KK 2 terminal boxes i e redundant version or with option S further combined connections available connections axial design AK Terminal box AR Burndy plug AC Connection cable Pulses per revolution Basic signal output Basic channel 0 A Pulse channel 90 B Each with inverted signals NG Option reference pulse with inverted signal N2 Reference pulse mechanically fixed with LED check red for display...

Страница 15: ...er Series connections radial design K Terminal box R Burndy plug C Connection cable L Fiber optic connection S 15 pole EMC industrial plug KK 2 terminal boxes i e redundant version Resolution 1024 signal periods per revolution Output signals 2 sinusoidal signals A and B each with inverted signals NG Option reference pulse with inverted signal ...

Страница 16: ... the forwarder directly on receipt of the goods about existing transport damages prepare pictures for evidence 4 3 Packaging disposal The packaging is not taken back and must be disposed of in accordance with the respective statutory regulations and local guidelines 4 4 Storage of packages devices Keep dry Keep packages dry and free from dust protect from moisture Protect against heat Protect pack...

Страница 17: ...e the signal frequency the length of the signal cable and the place of installation please refer to Chapter 3 2 Degree of protection To fulfil degree of protection requirements the diameter of the connection cable must correspond to that of the cable gland please refer to Chapter 11 dimension drawings Deep groove ball bearings FG incremental encoders are fitted with maintenance free greased for li...

Страница 18: ...arth cable are not included in the range of supply 2 Preparing the place of attachment Clean the motor shaft centering bolting surfaces and fastening threads check for damage Repair any damage 5 5 Mounting B5 type flange incremental encoders NOTES For a mounting example please refer to dimension drawing HM 09 M 57 263a Chapter 11 1 1 9 2 10 3 12 13 4 7 6 15 8 5 14 17 11 16 Figure 1 FG 40 construct...

Страница 19: ...ering 4 6 Fit the encoder 8 into both the centering 4 and coupling hub at the same time NOTES You must be able to mount the coupling without force Ream out the bores of used couplings if necessary NOTES If possible fit the device in a manner that ensures the cable gland points downwards Exchange the position of the cable gland 16 and the blanking plug 15 if necessary 7 Secure the encoder with 4 6 ...

Страница 20: ... grease the motor shaft 1 2 Fit coupling 2 onto motor shaft NOTES You must be able to mount the coupling without force Ream out the bores of used couplings if necessary NOTES We recommend our zero backlash torsion resistant double joint coupling HKD5 to attach B35 type encoders Please refer to the catalogue Torsion Resistant Couplings for Encoders 3 Secure the coupling hub on the motor shaft with ...

Страница 21: ...ith the grub screw or cheese head screw 11 depending on the coupling type 5 7 Mounting tolerances for construction type B5 and B35 NOTES Angle misalignment and parallel displacement between the motor shaft and the encoder shaft are mounting errors and should be kept as small as possible Mounting errors Cause radial forces to act on the encoder shaft Reduce the service life of the bearings and the ...

Страница 22: ...tional device Installation example see dimension drawing HM 09 M 102 245 Chapter 11 5 This design option makes it possible to combine up to four devices When supplied ex works the second shaft end is protected by a cover plate 3 secured with 6x M6x20 hexagon head screws 4 CAUTION Do not remove the housing cover secured with Torx screws These devices are not equipped with a second shaft end 1 Loose...

Страница 23: ...alf 5 with elastomer ring up to the collar of the shaft of the additional device 7 and secure by tightening the grub screw 6 NOTES The correct distance between both coupling halves has now been set 4 Mount the attachment 7 to the B 14 flange 2 of the rotary encoder 5 Fix the attachment 7 with 6 x hex bolts M6 x 20 8 8 For this step the mounting screws 4 of the cover can be used 6 7 5 4 7 2 Figure ...

Страница 24: ... contact is made with the bare cable shielding to ensure a good shield connection This type of shield connection should be preferred Alternatively if equipotential boning currents are anticipated it is possible to connect the cable shielding to a shield terminal in the terminal box A capacitor between the shield terminal and the encoder housing prevents the flow of equalizing current To achieve an...

Страница 25: ...utputs as this will destroy the device 7 Applicable to alternative shield connection only fit cable lug to cable shield and connect to the shield terminal please refer to the connection diagrams Chapter 12 NOTES To achieve a good shielding effect the cable shield be kept as short as possible 8 Close the terminal box cover NOTES Before closing the terminal box cover check and if necessary clean bot...

Страница 26: ... instructions contained in Chapter 2 when inspecting or working on the device NOTES Do not use a hammer or similar tool when installing the device due to the risk of damage occurring to the bearings or coupling 6 2 Dismantling the encoder Remove all electrical cables from the device before dismantling To dismantling the encoder follow the instructions given in Chapters 5 5 and 5 6 or 5 8 in the re...

Страница 27: ...s Supply voltage not connected Connect supply voltage Connection cable reversed Wire correctly Output signals subject to interference Unsuitable cable Use data cable with conductors arranged as twisted pairs and common shield Cable shield not connected Connect cable shield at both ends Cable routing not EMC compliant Observe applicable EMC guidelines when routing cables Signal interruptions Signal...

Страница 28: ...x 16 000 20 000 hours of operation higher levels of continuous load Check deep groove ball bearings are running smoothly and listen for running noises 9 Disposal 9 1 Disposal procedure The manufacturer is not obliged to take back the device The device is classed as electronic equipment and subject to the WEEE Directive observe local country specific laws when disposing of the device For informatio...

Страница 29: ...n_R12 2018 10 31 ID74490 doc 29 11 Dimension drawings Further dimension drawings on our website or on request 11 1 Construction type B5 flange FG 40 K With radial terminal box HM 08 M 57 221a FG 40 AK With axial terminal box HM 08 M 57 024a ...

Страница 30: ...mental Encoder FG 40 30 FG40_MANUAL en_R12 2018 10 31 ID74490 doc FG 40 KK Redundant version HM 08 M 57 223a FG 40 K Mounting example for construction type B5 with flange and coupling HK 522 HM 09 M 57 263a ...

Страница 31: ...cremental Encoder FG 40 FG40_MANUAL en_R12 2018 10 31 ID74490 doc 31 11 2 Construction type B35 flange and foot FG 40 K With radial terminal box HM 08 M 57 222a FG 40 KK Redundant version HM 08 M 57 224a ...

Страница 32: ...Incremental Encoder FG 40 32 FG40_MANUAL en_R12 2018 10 31 ID74490 doc FG 40 K Mounting example for construction type B35 With coupling HKD 522 HM 09 M 102 240a ...

Страница 33: ...Incremental Encoder FG 40 FG40_MANUAL en_R12 2018 10 31 ID74490 doc 33 11 3 Construction type B5 B14 flange with 2 shaft ends FG 40 K Construction type B5 B14 flange with 2 shaft ends HM 09 M 102 541 ...

Страница 34: ...Incremental Encoder FG 40 34 FG40_MANUAL en_R12 2018 10 31 ID74490 doc FG 40 KK redundant version HM 09 M 102 549 ...

Страница 35: ...al Encoder FG 40 FG40_MANUAL en_R12 2018 10 31 ID74490 doc 35 11 4 construction type B35 B14 flange and foot with 2 shaft ends FG 40 K construction type B35 B14 flange and foot with 2 shaft ends HM 09 M 102 280 ...

Страница 36: ...Incremental Encoder FG 40 36 FG40_MANUAL en_R12 2018 10 31 ID74490 doc FG 40 KK redundant version HM 09 M 101 548 ...

Страница 37: ...Incremental Encoder FG 40 FG40_MANUAL en_R12 2018 10 31 ID74490 doc 37 11 5 Mounting options FG 40 K FG 40 K with coupled unit HM 09 M 102 245 ...

Страница 38: ...Incremental Encoder FG 40 38 FG40_MANUAL en_R12 2018 10 31 ID74490 doc FG 40 KK FG 40 KK with coupled unit HM 09 M 102 627 ...

Страница 39: ...l Encoder FG 40 FG40_MANUAL en_R12 2018 10 31 ID74490 doc 39 11 6 Additional dimension drawings electrical socket design FG 40 R RR additional dimension drawing electrical socket design FG 40 R RR HM 09 M 102 270 ...

Страница 40: ...Incremental Encoder FG 40 40 FG40_MANUAL en_R12 2018 10 31 ID74490 doc FG 40 L LL additional dimension drawing electrical socket design FG 40 L LL HM 09 M 103063 ...

Страница 41: ...Incremental Encoder FG 40 FG40_MANUAL en_R12 2018 10 31 ID74490 doc 41 FG 40 S SS additional dimension drawing electric connection implementation FG 40 S SS 15 pole EMC HM 12 M 105755 ...

Страница 42: ...using of the encoder by the cable gland Alternatively the shield of the signal cable can be connected to K11 via a capacitor 10nF 500V to the housing of the encoder FG 40 Standard Terminal box 10 pole printed circuit spring terminal block type Phoenix ZFKDS Connection data wire section 0 2 1 5 mm Alternative Shielding FG 40 Standard without reference pulse Terminal box ...

Страница 43: ...ng tool Burndy No MR 8 GE 5 FG 40 Standard Burndy plug Connection cable 6x2x0 56 twin standard shielded Type HE 2LVCC CY AWG 20b acc to VDE 0881 Cross section 0 56 mm Temperature 20 C to 105 C Outside dia 10 1 mm shield is connected to casing other cables temperature ranges on request FG 40 Standard Connection cable Crimp contacts for cross sectional data of wire from 0 52 up to 1 5 mm ...

Страница 44: ...cable can be connected to K13 via a capacitor 10nF 500V to the housing of the encoder Alternative Shielding FG 40 Option 2F Terminal box 10 pole printed circuit spring terminal block type Phoenix ZFKDS Connection data Wire section 0 2 1 5 mm Shielding The shield of the signal cable can be connected directly to the housing of the encoder by the cable gland Alternatively the shield of the cable can ...

Страница 45: ...cable can be connected to K13 via a capacitor 10nF 500V to the housing of the encoder Alternative Shielding FG 40 Option B2 Terminal box 10 pole printed circuit spring terminal block type Phoenix ZFKDS Connection data Wire section 0 2 1 5 mm Shielding The shield of the signal cable can be connected directly to the housing of the encoder by the cable gland Alternatively the shield of the cable can ...

Страница 46: ...Incremental Encoder FG 40 46 FG40_MANUAL en_R12 2018 10 31 ID74490 doc FG 40 connection sheme PN 109 470 terminal box ...

Страница 47: ...Incremental Encoder FG 40 FG40_MANUAL en_R12 2018 10 31 ID74490 doc 47 FG 40 connection sheme PN 109 415 EMC industrial plug FG 40 connection sheme 649 Option S Burndy plug ...

Страница 48: ...Incremental Encoder FG 40 48 FG40_MANUAL en_R12 2018 10 31 ID74490 doc FG 40 connection sheme 148 400b Sine cosine output ...

Отзывы: