INSTALLATION, OPERATION & MAINTENANCE DATA SHEET

 

VSQ SERIES 60 AMP INTERLOCKED SWITCHED RECEPTACLES

 

 

 

 

 

 

 

APPLICATIONS

 

  VSQ  series  dead  front  interlocked  receptacle  with 

switch is suitable for use in hazardous locations. 

  Designed  for    supplying  power    to  fixed  or    portable 

electrical equipment. 

ELECTRICAL RATING

 

  Maximum  voltage  -  600  VAC  @  50-400Hz. 

Continuous Current - 60Amperes. 

INSTALLATION

 

  Carefully  Read  and  understand  the  following 

instructions  before  installation  &  operation  of  this 
device. 

 

Note: 

All  Installations  must  comply  with  Applicable 

Local,  National  Electrical  Code  and/or  Canadian 
Electrical Code. 

 

Note: 

VSQ  covers  can  not  be  used  on  VWSQ 

mounting  boxes,  which  are  intended  for  non- 
hazardous location installations. 

 

Warning: 

Make  sure  the  receptacle  assembly  is 

suitable for use in desired location per  applicable  local 
and/or  National  Electrical  Code.  Serious  damage 
and/or 

injuries  may  result 

due  to  improper 

applications.  Electrical  power  must  be  turned  OFF 
before  and  during  the  installation  &  maintenance. 
Fatal  injury  and/or  damage  may  result  by  not 
following these instructions. 

 

Mounting  Arrangement: 

Receptacle  assembly  must 

be  mounted  securely  onto  a  column,  wall,  or  other 
structure  that  is  able  to  support  the  device  and  the 
associated  conduit  system.  The  structure  is  to  be 
prepared for use of four (4) 

3/8” steel bolts (furnished 

by  others)  using  the  lugs  on  the  housing.  The 
spacings  are  as  shown  in  Fig.  1.  The  device  is 
equipped  with  factory  installed  hinges.  It  must  be 
mounted with the hinges on the left and  the receptacle 
in the downward direction. 

 

Conduit Installation:

 

1.  1 

1/2” NPT conduit entries are provided on the top 

and bottom of the housing. 
2.  All conduit entries must be sealed within 

18” of the 

enclosure as per National Electrical Code. 
3.  Make sure conduit entries are clean before 
installing conduit, close-up plugs, reducers, etc. 
Killark 

“LUBG” thread lubricant is recommended for 

this application. 

 

Warning: 

Use only copper cable or wire for the range 

indicated in the table. 

Use 75°C rated conductors 

(minimum).

 

 

Wire Range 

Strip Length 

Torque 

Switch 

#6 - #4 

0.750 inches 

30 in.-lb. 

Ground 

#16 - #6 

0.500 inches 

30 in.-lb. 

 

Wiring:

 

1.  Develop  and  establish  the  wiring  pattern  for  your 
system.  Locations  having  different  voltages  and/or 
frequencies 

must 

not 

have 

interchangeable 

attachment plugs.  Always test before energizing. 
2.  Make  sure  to  pull  sufficient  length  of  supply 
conductors to connect to the enclosed terminals. 
3. Strip the conductors to the length shown in table. 
4.  Connect  the  conductors  to  the  ground  and  phase 
terminals securely and tighten to the values shown in 
the table. 

 

Inspect  &  Clean  Flange: 

The  machined  flange 

surface  of  both  the  box  and  cover  must  be  smooth, 
free  of  nicks,  scratches,  dirt,  or  any  foreign  particle 
build-up  that  would  prevent  proper  seating.  Surfaces 
must seat fully against each other to provide a proper 
flame  path  joint.  Clean  surfaces  by  wiping  with  a 
clean,  lint  free  cloth.  Apply  a  light  coating  of 

“LUBG” 

lubricant to flange surface. 

 

Cover Securement: 

Close  the cover  then install  and 

tighten all cover bolts to 25 ft.-lb.  Make sure no cover 
bolts  are  omitted.  Use  only  those  bolts  supplied  with 
the device.  Check the bolted joint with a 

.0015” feeler 

gauge.  The gauge must 

not 

enter the joint more than 

1/8” at any point. 

 

Caution: 

Missing bolts or an improper joint can result 

in  an  explosion,  creating  the  potential  for  serious  or 
fatal physical injury and/or property damage. 

 

Cover 

Replacement: 

The 

power 

must 

be 

disconnected before removing the cover. Remove the 
bolts  and  reverse  the  wiring  procedure.  Once  the 
conductors  have  been  detached,  remove  the  screws 
that hold the cover to the hinges (4 total). Line up the 
new  cover with  the  hinges  and  reinstall  the  hinge 
screws.  Once  the  hinges  are  attached  repeat  the 
wiring,  inspect  &  clean  flange  and  cover  securement 
procedures. 

CLASS I, GROUPS B,C,D; CLASS I ZONE 1, GROUPS IIB, IIA +H

2

; CLASS II, GROUPS F & G; & CLASS III 

HAZARDOUS LOCATION ENCLOSURE TYPES 3, 4, 4X & 12.

 

All Installations Must Comply With Applicable Local, 
National Electrical Codes, and/or Canadian Electrical 
Code.

 

To Prevent Ignition of Hazardous Atmospheres Do Not 
Use in Class II, Group E Locations that Contain 
Electrically Conductive Dusts.

 