Vertical Coverage
Horizontal Coverage
35'
Mounting
Height
36" to 54"
(91.44 to 137.16 cm)
5°
5°
35'
16'
16'
Vacancy and Occupancy sensors use passive infrared detection and a microcontroller to maximize energy savings and
minimize turning off lights in an occupied room.
Hubbell offers 4 models:
Vacancy Sensor: RMS100, RMS120
120VAC, 60 Hz (Ivory, White, Almond, Light Almond)
Occupancy Sensor: RMS101, RMS121
120VAC, 60 Hz (Ivory, White, Almond, Light Almond)
Lighting Load:
120VAC: 25Watts minimum, 500Watts maximum incandescent only (Do not use with
fluorescent lamps).
Time Delay:
Manual adjustment behind front press switch: 30 second minimum, 30 minutes maximum.
Daylight Control (
Occupancy Sensor Only)
:
Press one button to set ambient light level (Photocell).
Manual Override Front Press Switch (FPS):
Switches lights “on” or “off”, (See Front Press switch Basic
Operation Below). Note: FPS must be pressed to turn light on.
Motion Indicator:
Highly visible green LED.
Reset to Factory Setting:
Hold front press switch for 10 seconds resets the sensor to the factory settings.
50% dim down:
Lights dim to 50% 30 seconds before they switch off.
Coverage Area approximately 800ft² (74m²) See coverage area below.
Passive infrared (IR) sensors are activated by changes in IR temperature in the coverage area.
The product must be installed in the line-of-sight of the occupant. The sensor should not be installed:
s:KHUHYLHZRIRFFXSDQWLVREVWUXFWHG
s,QYLHZRIRSHQGRRUZD\VZKHUHKDOOZD\WUDIILFPD\EHGHWHFWHGDQGDFFLGHQWDOO\DFWLYDWHOLJKWV
s,QYLHZRIGLUHFWVXQOLJKWRUVWURQJUHIOHFWHGOLJKWVRXUFHV
s$ERYHEDVHERDUGKHDWHUVRUQHDUIRUFHGDLUGXFWV
s2XWGRRUVLQWKHUDLQQHDUDVKRZHUVWHDPVRXUFH)RULQGRRUXVHRQO\
NOTICE:
Designed for hard wire circuits only, do not use to control receptacles. For installation by a qualified electrician
in accordance with national and local electrical codes and the following instructions.
CAUTION: RISK OF ELECTRIC SHOCK. Disconnect power before installing.Never wire energized electrical
components. Mandate required OSHA lockout, tag out procedures.
CAUTION: USE COPPER CONDUCTORS ONLY.
CAUTION: Use only in indoor, dry locations. Sensor’s maximum operating ambient temperature = 50ºC.
CAUTION: To Reduce the Risk of Overheating And Possible Damage To Other Equipment, Do Not Install
To Control A Receptacle, A Motor-Operated Appliance, A Florescent Lighting Fixture, Or A Transformer-
Supplied Appliance.
Single-Gang Installation ONLY
Hubbell Incorporated (Delaware)
185 Plains Road
Milford, CT 06461-2420
(203) 882-4800
PD2203
Passive Infrared Vacancy Sensors RMS100, RMS120 and
Passive Infrared Occupancy Sensors RMS101, RMS121
INSTALLATION INSTRUCTIONS