Remove four #8-32 pan head screws [1] 
from top corners of floor box assembly 
and retain.
Remove transition [2] and mounting plate 
[3] assemblies from box and retain.
Install leveling screws [4] as shown in 
FIGURE A.
Make conduit connections in accordance 
with application and applicable electric 
codes.  2" trade size conduit hubs, 
(CFBHUB2) may be used in place of 
Knockout plates [5] as needed.
For feed-thru wiring, remove non-metallic 
dividers [6] as necessary.
Reinstall  transition [2] on top of the 
mounting plate assembly [3].  Secure using
#8-32 pan head screws [1] in corners.
Cover visible openings and screws that 
penetrate the floor box with tape to 
prevent concrete from entering the box.
Position the floor box with the temporary 
cover [7] even with slab level.  Use leveling
screws [4] and wire to keep the floor box 
from moving during concrete pour.  
Minimum depth of pour is 3.75 inches 
[95.3 mm]
Verify that flat head screws [8] holding the
temporary cover [7] are secure.  After 
tightening, cover screw heads with tape to
aid in removal later.
Pour concrete flush to the top of the 
temporary cover [7].

1.
 
 
2.
 
3.
 
4.
  
 
 
 
5.
 
6.
 
 
7.
 
 
8.
 
 
 
 
 
9.
  
  
 
10.

BEFORE CONCRETE POUR, SEE FIGURE A

CAUTION:  RISK OF ELECTRICAL SHOCK.  Disconnect power before installing or servicing. 
NOTICE:  For installation by a qualified electrician in accordance with all national and local electrical codes, 
communications standards, the following instructions and any instructions included with individual devices.
NOTICE:  Insure data/communications circuits are separated from lighting/power circuits in accordance with the NEC  and
CE Code requirements.
 
Use with CFBS1R8CVRxx series round covers.

Adjust height of cover support collar flush to just below the finished floor.  Cover support collar is adjustable for 
finished floors of 0 inches to .25 inches [0.0 - 6.4 mm] thick.  Tighten mounting screws [12] to 10 - 15 lbs-in torque 
[1.1 - 1.7 N-m].  For thicker floor finishes use accessory collars (CFB8RCVRR series), sold separately.
Seal the gap around the cover support collar [11] with a continuous bead of electrical grade type RTV silicone sealant 
(SEE FIGURE E).
Use the provided floor gasket or apply a 1/4 inch [6.3 mm] thick continuous bead of electrical type  of RTV silicon 
sealant compound fully around the perimeter on the underside of the flange [13].
Attach flange [13] to the cover support collar [11] using #8-32 flat head screws [14] provided with the cover.

18.
 
 
19.
 
20.
 
21.

Wiring Device - Kellems
Hubbell Incorporated (Delaware)
40 Waterview Dr.
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com

CFB6G30R/CFB6G30RCR   6 GANG RECESSED FLOOR BOX FOR

ROUND COVER   Installation Instructions

PD2593

04/14

ENGLISH

A

FIGURE

E

FIGURE

6

5

1

2

3

4

7

8

SEAL ALL AROUND