003-2608 

 

 
 
 
 
 
 

Dual-Lite

®

 Trident TRF 

 Battery Cabinet 

10kVA (UL924 System) 

10-30kVA (Alternate Runtimes) 

USER MANUAL

  

 
 

Содержание Dual-Lite Trident TRF Series

Страница 1: ...003 2608 Dual Lite Trident TRF Battery Cabinet 10kVA UL924 System 10 30kVA Alternate Runtimes USER MANUAL...

Страница 2: ...y the product described herein in order to improve it at any time and without notice For technical assistance contact Dual Lite s Technical Support Center at 1 800 848 6439 Technicians are available d...

Страница 3: ...es Battery acid can cause burns to skin and eyes If acid is spilled on skin or in eyes flush acid with fresh water and contact a physician immediately e Equipment should be installed where it will not...

Страница 4: ...RNING This product contains Valve Regulated Sealed Acid Batteries These batteries contain lead a neurotoxin and sulfuric acid a corrosive Additionally the energy stored in the batteries can present a...

Страница 5: ...Symbols iii Table 2 Model Floor Loadings 3 Table 3 Terminal Tightening Torques and Wires Sizes 11 Table 4 Replacement Batteries and Operating Temperatures 15 Figure 1 The Trident TRF Battery Cabinet 1...

Страница 6: ...to prevent loss of valuable electronic information and minimize equipment downtime During brownouts blackouts and other power interruptions batteries provide emergency power to safeguard operation 1...

Страница 7: ...fully charged the useful life of the batteries will be reduced if they are subjected to high temperatures The operating temperature range of 15o C to 40o C 5o F to 104o F must not be exceeded for even...

Страница 8: ...he equipment 2 Send a copy of the damage claim within 15 days to your service representative 2 2 Floor Loading When planning the installation consider the battery cabinet weight for floor loading The...

Страница 9: ...ve the cabinets from the pallet To remove the battery cabinet from the ship pallet 1 Make sure the forklift is rated for the cabinet weight 2 Remove all banding wrapping and foam protectors 3 Remove a...

Страница 10: ...ur 4 leveling feet are raised so that they will not touch the floor when the cabinet is placed on the floor 8 Lift the cabinet with a forklift from the rear of the unit one to two inches 1 2 2 5 5cm a...

Страница 11: ...Do not tip the cabinet more than 15 degrees from vertical 2 5 Placing the Cabinet Once the cabinet has been rolled into position remove the front panel to access the front leveling feet by pulling the...

Страница 12: ...sest to the UPS WARNING TB3 is energized at all times Opening the circuit breakers does not remove power from this terminal block DANGER Only qualified service personnel such as a licensed electrician...

Страница 13: ...ver by removing the 10 ten screws mounting it to the enclosure 8 Conduit landing plates are located at the front bottom of the base to accommodate bottom wire entry to the cabinet see Figure 7 Remove...

Страница 14: ...CONTROL CABLE ENTRY 1 75 44 5mm X 1 75 44 5mm REAR Figure 7 Bottom View of Cabinet PRODUCTS CO R U1 R3 R2 R1 Q1 J3 J2 J1 F1 D2 D1 BATTERY CIRCUIT BREAKERS B VERSIONS ONLY BATTERY FUSES BATTERY BREAKER...

Страница 15: ...battery cabinet to TB1 of the second B battery cabinet Repeat these steps for additional B cabinets Use wire sized per local codes 6 AWG 75 C copper wire minimum to 2 0 AWG maximum When a N version c...

Страница 16: ...hite See Figure 13 Repeat this procedure for the other battery cabinets if present 8 Reinstall the front inner panel on each battery cabinet using the screws provided 9 After the internal batteries in...

Страница 17: ...of the UPS connect the battery cabinet interface connector TB4 to the UPS per Figure 10 If any additional battery cabinets are N versions no other connections are needed If a Dual Lite maintenance byp...

Страница 18: ...ted the batteries must be disconnected by unplugging the cables to the battery trays If it is necessary to remove the cables from the batteries the connections should be marked in a way that no confus...

Страница 19: ...o not take away the external support until the extension limit tabs on the upper sides of the battery tray are inserted past the notches on the upper edge of the battery shelf see Figure 12 Always ins...

Страница 20: ...rrosive Additionally the energy stored in the batteries can present a shock hazard and a burn hazard Batteries should be serviced by trained personnel Appropriate safety precautions must be observed i...

Страница 21: ...Page 16 Figure 13 Cabinet Schematic...