MP15 Jockey Pump Controller 

3

 

 

 

Publication 245-EN – November 2013 

 

 
Installation 

The controller has been assembled and wired at the factory with the highest 

workmanship standards. All wiring and functions have been thoroughly tested to 

ensure correct operation when properly installed. 

Receiving, Handling, and Storage 

1.

 

Immediately upon receipt, carefully unpack and inspect the controller 

for damage that may have occurred in shipment. If damage or rough 

handling is evident, file a damage claim with the transportation carrier 

immediately. 

2.

 

If the controller must be stored, cover it and then place it in a clean, dry 

location. Avoid unheated locations, where condensation can result in 

damage to the insulation or corrosion of metal parts. 

Precautions 

CAUTION 

To avoid risk of 

SERIOUS INJURY or DEATH

, and to 

avoid damage to the controller, READ THIS SECTION 
CAREFULLY.  If questions or concerns still exist, 
contact the Metron factory for further 
clarification. 

 

If work must be carried out on the motor or controller, ensure the controller is 

ISOLATED AND LOCKED OFF from the AC mains supply before work 

commences.  Lockout/Tag out procedures should be followed in accordance 

with OSHA standard and any local standards that may apply. 
During installation and maintenance, to prevent automatic starting of the motor 

ensure the controller HOA Switch is in the Off position. 
To avoid risk of serious electric shock, 

never

 energize the controller with the 

access door open unless absolutely necessary. 
If the access door to the interior of the panel has to be opened when the panel is 

energized, take caution that high voltage is present.  

Installation Instructions 

Mounting 

The controller should be mounted using appropriate fixing methods: 

Содержание Metron MP15

Страница 1: ...ration maintenance and system setup information for Metron Model MP15 Jockey Pump Controllers Section Page Introduction 2 Installation 3 Operation of the Controller 5 Operator Interface Device OID Use...

Страница 2: ...ormal water pressure and prevent unnecessary cycling of the main fire pump s Approvals Metron MP15 controllers are listed by Underwriter s Laboratories Inc in accordance with UL508A Standard for Indus...

Страница 3: ...d risk of SERIOUS INJURY or DEATH and to avoid damage to the controller READ THIS SECTION CAREFULLY If questions or concerns still exist contact the Metron factory for further clarification If work mu...

Страница 4: ...he installer is responsible for ensuring no metallic foreign objects such as drilling chips etc fall inside the controller onto the electrical circuit Failure to observe this could result in damage to...

Страница 5: ...may fluctuate slightly due to small leaks in the system The use of this small pump will eliminate frequent starting of the main pump The Jockey Pump Controller automatically starts the Jockey Pump Mo...

Страница 6: ...erly installed all external connections have been made and the Motor Starter Protector is closed Manual Operation To manually start the jockey pump motor turn the HOA Selector to the Hand position Thi...

Страница 7: ...ist of windows They are denoted onscreen with an arrow to the right of the text Set Points which display the set point name and its current value Use the EN T E R UP and DO WN buttons to navigate thro...

Страница 8: ...sure HOA switch position and status of the pump If there is no user activity on the OID after five minutes the onscreen window will automatically return to the Home window Alarms and Events When there...

Страница 9: ...ndow choose Log Out Note The Log Out menu item will not be displayed if the current user login status is not logged in Configuring System Set Points WARNING To configure the system set points place th...

Страница 10: ...the UP and DO WN buttons to change the value of the current step b Use the EN T E R button to confirm with current step 3 When the current set point configuration is complete the next set point will...

Страница 11: ...igation Tree Home Window System Set Points User Preferences Tech Screen USB Memory Stick About Window Calibrate Pressure Sensor Language Pressure Unit Screen Brightness Start Pressure Stop Pressure St...

Страница 12: ...automatic start of the pump when a low system pressure condition occurs Range 0 999 Seconds Minimum Run Time The minimum time that the pump must run before an automatic stop Range 0 999 Seconds Short...

Страница 13: ...mber 2013 Set Point Definition Language Selects the onscreen language Pressure Unit Selects the system pressure unit PSI or BAR Screen Brightness Adjusts the brightness of the screen backlight Calibra...

Страница 14: ...Pump Running LED should turn on 3 Turn the HOA switch to the Off position 4 The pump should stop immediately and the Pump Running LED should turn off Automatic Pressure Start 1 Turn the HOA switch to...

Страница 15: ...g manual or automatic Pump Stopped The pump has stopped running manual or automatic Pressure Sensor Fault A pressure sensor fault alarm has occurred HOA Switch Fault An HOA Switch fault alarm has occu...

Страница 16: ...t regulations which is applicable in all EC countries At the end of the service life of the equipment the company offers to collect and dispose of this equipment in accordance with regulations in forc...

Страница 17: ...21 Publication 245 EN November 2013 Printed in USA Replacement Parts For replacement parts contact your local Metron sales office or the Metron factory at United States Telephone 1 336 434 2800 FAX 1...