background image

5

200mA

1A

5A

10A;

3

After the current is selected, click "start measurement" to display "please wait while

charging" to enter the test state. After a few seconds, the test result will be displayed, as

shown in figure 3

Figure 3

After displaying the test results, click

to directly switch the "Tap position" without

returning to the main interface. After switching tap position, wait patiently for A few

seconds for the test results. Next, you can save the test results by "Local storage", or

click "U disk storage" and "Print". Click "Return to main page" and "Return to main

interface"

;

4

Click "Data management" in figure 1 to enter the data query interface, as shown in

figure 4

Содержание HZ-3110B

Страница 1: ...HZ 3110B Transformer DC Resistance Tester Huazheng Electric Manufacturing Baoding Co Ltd...

Страница 2: ...al and operate and maintain the instrument according to the manual to prolong its service life Just a light press the test will be completed automatically is the operating characteristics of this inst...

Страница 3: ...tion 1 II Configuration 1 III Safety Measure 2 IV Presentation Of The System 3 V Instrument Operation Instruction 3 VI Test And Operating 7 VII Communication 9 VIII Caution 9 IX After sales Services 1...

Страница 4: ...ne to control the instrument through the special software The test data is stored in a fixed format on the mobile phone which is convenient for data query at any time 2 The maximum output voltage of t...

Страница 5: ...or computer communication and U disk data storage 10 It can print test results with its own surface micro printer III Safety Measure 1 Output current automatic 20mA 40mA 200mA 1A 5A 10A 2 Resolution 0...

Страница 6: ...otection I I Current output terminals I is the positive current I is the negative current V V Voltage input terminals V is the positive voltage V is the negative voltage RS232 Universal series interfa...

Страница 7: ...lick to delete click to confirm click to back Convert temperature Click will bring up to set temperature click to delete click to confirm click to back Tap position Click will bring up setting click t...

Страница 8: ...displaying the test results click to directly switch the Tap position without returning to the main interface After switching tap position wait patiently for A few seconds for the test results Next y...

Страница 9: ...in figure 1 to enter the parameter setting interface as shown in figure 5 Figure 5 Brightness adjustment according to the scene environment the screen brightness can be adjusted by moving the button L...

Страница 10: ...Operating 1 Connection Connect the testing product to the device through test terminal joint firm meanwhile insure a well connection of the earthing wire A Single phase testing method to see the follo...

Страница 11: ...8 A B C I I Measurement device O V V a b c Testing product Pic 3 A B C I I Measurement device O V V a b c Testing product Pic 4...

Страница 12: ...or the device to match successfully 4 Open the software and click the gray Bluetooth icon in the upper right corner of the homepage Select the device that just matched successfully in the pop up menu...

Страница 13: ...No irrelevant items are allowed to be stacked on and around the equipment panel during the test 9 When replacing safety pipes and fittings please use the same model as this instrument see technical sp...

Страница 14: ...1 X Packing List No Item Qty 1 Main engine 1 2 Power line 1 3 Fuse pipe 2 4 Red test line 1 5 Black test line 1 6 Print paper 1 7 Test sample Standard resistance 1 8 Serial port line 1 9 Ground lead 1...