Process

value

offset

-99

99.9

~100

100.0

)℃

Used

to

correct

the

measurement

error

generated by the sensor and

thermocouple compensation

wire

0

rt

Insensiti

ve zone

(dead

zone)

0.4~100

100.0

)℃

Insensitive area of position

type and alarm function, the

same dF of position type and

alarm function of instrument

with position type control

0.4

dF

Alarm

point

setting

-1999~1999

Alarm point setting, when AL

0, it is upper limit alarm;

when AL

0, it is lower limit

alarm

50

AL

Control

cycle

(heating

side)

1~100s

Relay output

20s,

SSR and thyristor switch

3s

Automatically flip the output

state

202

T

Alarm

delay

time

0~3600s

When the measured value

reaches the alarm value, the

alarm relay will only output

after Ct time has passed

0

Ct

Proporti

onal

band

(heating

side)

1~300

Proportion

is

used

for

adjustment, the larger the P,

the smaller the proportional

effect, the lower the system

gain, and it only acts on the

heating side

30

p

Integrati

on time

(re-adjus

t time)

0~3600s

Integral action time constant,

the larger the I, the weaker

the integral action

240

I

Different

ial time

(presetti

ng time)

0~3600s

Differential

action

time

constant, the larger the D,

the stronger the differential

action

60

D

Passwor

d lock

0~2

0: All parameters can be

modified

1: Only the given value (SP)

can be modified

2: All parameters cannot be

modified

0

Lc

Do not press the key for more than 4 seconds to enter the standard mode, and it will
automatically return within 1 minute. Some function parameters may not be
changed.