
Figure 6-25 Installing a T/H sensor
Step 5 Choose Monitoring > System > ECC800-Pro > Controls and delete the device
failing in communication.
Step 6 Choose Monitoring > Aisle > T/H Sensor Group and check whether the T/H
sensor works properly. If yes, the T/H sensor is functional.
Step 7 Choose Home > Plan View and add a new T/H sensor in the appropriate position.
----End
6.3.17 Replacing a Temperature Sensor
Prerequisites
●
Recommended tools and materials: diagonal pliers, insulation tape, cable tie,
step ladder (2 m)
●
A temperature sensor needs to be replaced.
●
Spare temperature sensors of the same model are available and functional.
Procedure
Step 1 Cut the cable ties on the temperature sensor using diagonal pliers, and remove
the network cable from the temperature sensor.
FusionModule2000-S Smart Modular Data Center
User Manual
6 Operation and Maintenance
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
262