Procedure
Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery
Maint.
Step 2 Tap Start on the right of Group Capacity Test to start a group capacity test.
Figure 7-19 Starting a group capacity test
NO TE
The group capacity test automatically stops in any of the following cases:
● The minimum cell voltage reaches 2.75 V.
● The load fluctuation exceeds 20%.
● An alarm is generated.
The test is complete when the minimum cell voltage reaches 2.75 V. The test data is
obtained from the group capacity test. Save the test data obtained from the latest 36 tests.
----End
7.7.3 Downloading the Test Data
Context
If the UPS does not communicate with SmartLi 3.0, batteries are managed as
lead-acid batteries by default and the battery information is subject to the data
displayed on the SmartLi or NMS.
Procedure
Step 1 On the WebUI, choose Query > Battery Test Records, choose logs that need to be
queried from the Log drop-down list box, and click Query.
Figure 7-20 Battery Test Records
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
7 Single UPS Commissioning