Figure 7-3 BCB connection settings
----End
7.1.6 (Optional) Setting Parameters for the Top Air-Flow
Cabinet
Prerequisites
A top air-flow cabinet is installed..
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set Top outlet
cabinet to Enable.
----End
7.1.7 (Optional) Configuring the Bottom Cabling Cabinet
Prerequisites
The bottom cabling cabinet has been deployed.
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set Bottom
cable entry cabinet to Enable.
----End
7.1.8 (Optional) Setting the Backfeed Protection Card
Prerequisites
A backfeed protection card is installed.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)