The following procedure applies to installation against a wall. If cabinets are
not installed against a wall and there is operation space at the rear of the
cabinets, you need to install the cabinet combination screws at the rear and
the anchor screws at the bottom.
6.4.4.1 Installing Cabinets
Installation on the Floor
NO TICE
Ensure that the installation floor is flat.
Step 1 Determine the positions for installing cabinets on the mounting surface based on
holes in the marking-off template.
NO TE
● A: mounting holes on the channel steel
● B: mounting holes on the floor
Figure 6-172 Hole dimensions (unit: mm)
(1) Top air-flow cabinet
(2) UPS
(3) Inductor cabinet
Step 2 Use a hammer drill to drill holes for installing expansion bolts and then install
expansion sleeves in the holes.
Step 3 Install the accessories of the top air-flow cabinet.
1. Remove the rear door panels from the UPS cabinets.
2. Secure the PC panels to the inner side of the rear door panel from the outer
side of the rear door using plastic rivets.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
6 Installation
Issue 05 (2021-10-13)