UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
5 Operations
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
139
Procedure
Step 1
After confirming that the battery string is properly connected, switch on the battery string
input circuit breaker. If there are multiple battery strings, switch on the circuit breaker for
each battery string and then the general circuit breaker between the battery strings and the
UPS. The
No battery
alarm on the MDU disappears.
Step 2
Turn on the downstream output switch to supply power to loads.
----End
5.1.5 (Optional) Setting Parameters for the BCB Box
Prerequisites
A BCB box is installed.
Procedure
Step 1
Choose
Settings
>
Dry Contact Set
, set
MUE05A connection
to
Enable
, and set
BCB
connection [OL]
and
Battery breaker [STA]
to
Enable
.
Figure 5-4
BCB connection settings
----End
5.1.6 (Optional) Setting Parameters for the Top Air-Flow Cabinet
Prerequisites
A top air-flow cabinet is configured.
Procedure
Step 1
Choose
System Info > Settings > System Settings
, and set
Top outlet cabinet
to
Enable
.
----End