UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Issue 02 (2017-02-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
238
Figure 5-47
Querying historical alarms
You do not need to query logs. Choose
Query
>
Logs
, click
Export
, and save the file.
Step 2
Click
Query
, and you can see the corresponding historical alarms.
Figure 5-48
Exporting historical alarms
Step 3
Click
Export
and save the displayed webpage.
----End
5.12 Setting Hibernation Mode
When the load power is small and stable, the inverters in some power modules shut down so
that these power modules enter hibernation state and the other power modules bear all the
load power. This improves the system efficiency, reduces power consumption, and increases
the power module service life.