UPS5000-E-(25 kVA-75 kVA)-BF
User Manual
3 Installation
Issue 07 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
60
Figure 3-15
Securing the antiseismic kits to the floor
----End
3.2.2.2 IP21 component
IP21 component installing on the top of the cabinet, it prevents water from dropping into the
cabinet, protecting the cabinet to IP21.
Figure 3-16
IP21 component
3.2.2.3 Installing a Top Outlet Kit
Context
When the UPS is installed against the wall, install the top outlet kit to ensure heat dissipation.
Procedure
Step 1
Remove the top cover from the UPS cabinet rear.