UPS5000-E-(25 kVA-75 kVA)-BF
User Manual
2 Overview
Issue 07 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
26
Figure 2-13
Rear view of a battery module
(1) Connector
Functions
The battery module is pluggable.
The battery module can house ten 7 Ah–9 Ah/12 V lead-acid batteries. The battery
dimensions (H x W x D) are 151 mm x 94 mm x 65 mm.
The front panel has status indicators which can show the faulty status of the module.
A battery module is configured with a battery detection unit which detects the battery
module status in real time and reports data to the MDU through CAN.
Specifications
Dimensions (H x W x D): 160 mm x 108 mm x 786 mm
Weight:
−
< 6 kg (excluding batteries)
−
< 36 kg (including batteries)
2.3.5 Surge Protection Box
The surge protection box is used to improve the surge protection function for the UPS. It
applies to the power system with three-phase, four-wire, and PE. If the surge protection box is
configured, the UPS can provide 5 kA surge protection.
The three indicators on the surge protection box indicate its working status. When the UPS is
powered on and the surge protection box runs properly, all the three indicators are steady on.
If any indicator is off, the surge protection box is faulty.
box.