UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
90
Figure 3-40
Silk screens on the system signal interface board in power cabinet 1
Table 3-10
Mapping between the cables in the bypass cabinet and the ports on the system signal
interface board in power cabinet 1
Bypass Cabinet
Cable Name
Bypass Cabinet
Cable No.
Silk Screen on
System Signal
Interface Board in
Power Cabinet or
Cable No.
Quantity
Bypass module
DL37 cable
W301_J21
J21
1
W303_J24
J24
1
ECM 8-pin cable
W305_J22
J22
1
ECM system
monitoring bus
W307_J25
J25
1
CT cable
W309_J26
J26
1
Switch cable
Full
configuration:
04091625-06
Standard
configuration:
SW1310
04091626-23
1
A standard configuration model has only one switch cable (maintenance bypass switch). A full
configuration model has three switch cables (output switch, maintenance bypass switch, and bypass
input switch). The following figure describes how to connect cables for combined cabinets using a full
configuration model as an example.