UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
247
Figure 5-10
BCB connection setting
----End
5.2 Shutting Down and Powering Off the UPS
Context
After the inverter is shut down, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is not normal, the UPS supplies no power. Before shutting down the UPS, ensure
that all loads have shut down.
Procedure
Step 1
Shut down the inverter.
On the LCD
a.
On the main screen, tap
Common Functions
. Tap
Inv. OFF
.
b.
If no user is logged in, enter a user name and password, and tap
on the
login screen displayed.
c.
In the displayed dialog box, tap
Yes
to shut down the inverter.