UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
4 LCD and WebUI
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
106
Number
Area
Function
1
Running status area
Displays the power flow and UPS running information.
2
Menu bar
Displays alarms and real-time data, sets parameters, and provides control
commands.
The
Active Alarms
page is displayed by default.
3
Information area
Displays system monitoring information.
4.3.2.1 Parameter Settings
Figure 4-33
Parameter settings
System Settings
Item
Description
Default Value Value Range
High ambient
temperature
alarm threshold
(°C)
An alarm is generated when the
ambient temperature reaches or
exceeds the threshold specified
by this parameter.
55
40–60
Low ambient
temperature
alarm threshold
(°C)
An alarm is generated when the
ambient temperature is lower
than the threshold specified by
this parameter.
–10
–20 to 0
EPO detection
Indicates whether to enable
emergency power-off (EPO).
EPO is performed only when this
parameter is enabled and the
EPO switch is triggered.
When
EPO detection
is changed
from
Disable
to
Enable
, check
that the EPO cable is connected
correctly.
Disable
Disable, Enable
Bus capa. life
If this parameter is set to
Enable
,
the UPS detects the bus capacitor
lifespan.
Disable
Disable, Enable
Paral. sys.
When customer loads are light,
Disable
Disable, Enable