UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
4 LCD and WebUI
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
101
Item
Description
BP/SYSMT
If the BP/SYSMT switch is set to
Enable
, the port has
dry contact signal access. Using the port depends on
the status of the BP/SYSMT switch.
BP/SYSMT switch function
If the BP/SYSMT switch is set to
Enable
, this
parameter is displayed on the screen. Set this
parameter to determine whether the port is used to
detect the status of the PDU bypass input switch, or
system maintenance switch.
Settings Wizard
When the UPS starts for the first time or restarts after restoring factory settings, the settings
wizard automatically starts.
After first startup, set basic parameters, including the language, date and time, network
parameters, and common parameters.
Restore Default Settings Screen
Restore default settings after the inverter shuts down.
Default settings can be successfully restored only after you set DIP1, DIP2, and DIP3 on the DIP switch
to ON, ON, and OFF respectively.
4.2.5 Control
On the
Main Menu
screen, select
Control
and press
. The login screen for accessing the
Control
screen is displayed. The preset password is
000001
. After you enter the password,
press
.
Figure 4-28
Control screen
Starting the Inverter
You can start the inverter manually by pressing
Startup
.