Lithium battery
(3 U)
Reserved space
(1 U)
10 kVA UPS
(2 U)
UPS2000-H-(6 kVA
–
10 kVA) Quick Guide
01
Installation Preparations
Model
Weight
Dimensions (H x W x D)
UPS2000-H-6KRTL-Li
14 kg
43 mm x 430 mm x 514 mm
UPS2000-H-10KRTL-Li
17 kg
86 mm x 430 mm x 514 mm
Issue: 02
Date: 2021-10-13
1.
Before installing the devices, read the user manual carefully to get familiar with product information and safety precautions.
2.
Use insulated tools during installation.
3.
Only engineers certified by Huawei or its agents are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the UPS faults
caused are beyond the warranty scope of Huawei.
4.
When routing power cables and communications cables, prevent cables from being scratched by cabinet components.
1
Unit: mm
6 kVA UPS
(1 U)
Lithium battery
(3 U)
Reserved space
(1 U)
UPS Dimensions and Space Planning (6 kVA)
Rack-mounted
Tower-mounted
T/H sensor
Ethernet
SNMP
User equipment
Dry Contact Card
Model
Wiring Terminal
Number
of Phases
Rated Voltage
External Circuit
Breaker
Cable Cross-sectional
Area
Terminal Type
Note
6 kVA (single-
phase input
single-phase
output)
AC input
L/N/PE
1
220 V AC/230 V
AC/240 V AC
50 A (feature C)
10 mm
2
OT-10 mm
2
-M6 terminal
M4 screw tightening torque
:
1.2 N·m
Torque for tightening screws
: 4.8 N·m
Notes:
•
Use flexible conductors with a working
temperature of 90
℃
or softer conductors
for power cables. Cables with solid
conductors or twisted conductors may fail
to be installed.
•
If there is no battery bus bar (BBB) box,
connect battery cables to the UPS. Select OT
terminals based on the battery cables.
•
a: The lithium battery is equipped with a
circuit breaker.
•
b: In bypass mode, the UPS obtains power
from phase A. The input current is the
three-phase total current.
AC output
L/N/PE
1
40 A (feature D)
6 mm
2
OT-6 mm
2
-M6 terminal
Battery
+
2
54 V DC
160 A
a
2 x 25 mm
2
OT-25 mm
2
-M6 terminal
-
2 x 25 mm
2
PE
-
2 x 6 mm
2
OT-6 mm
2
-90
°
bending-M4
terminal
10 kVA (single-
phase input
single-phase
output)
AC input
L/N/PE
1
220 V AC/230 V
AC/240 V AC
80 A (feature C)
16 mm
2
OT-16 mm
2
-M6 terminal
AC output
L/N/PE
1
63 A (feature D)
16 mm
2
OT-16 mm
2
-M6 terminal
Battery
+
2
54 V DC
250 A
a
2 x 35 mm
2
OT-35 mm
2
-M6 terminal
-
2 x 35 mm
2
-
PE
2 x 6 mm
2
OT-6 mm
2
-M6 terminal
10 kVA (three-
phase input
single-phase
output)
AC input
L/N/PE
3
380 V AC/400 V
AC/415 V AC
80 A
b
(feature C)
16 mm
2
OT-16 mm
2
-M6 terminal
AC output
L/N/PE
1
63 A (feature D)
16 mm
2
OT-16 mm
2
-M6 terminal
Battery
+
2
54 V DC
250 A
a
2 x 35 mm
2
OT-35 mm
2
-M6 terminal
-
2 x 35 mm
2
PE
-
2 x 6 mm
2
OT-6 mm
2
-M6 terminal
Lithium battery
+
2
54 V DC
-
25 m
2
OT-25 mm
2
-M6 terminal
-
25 mm
2
PE
6 mm
2
OT-6 mm
2
-M6 terminal
Unit: mm
Rack-mounted
Tower-mounted
UPS Dimensions and Space Planning (10 kVA)
02
Installing a UPS
Installing Optional Components
6 kVA UPS
(1 U)
Lithium battery
(3 U)
Subrack
Lithium battery
(3 U)
10 kVA UPS
(2 U)
Subrack
The 4G module is
connected to the USB
port of the SNMP card
through a USB
extension cable. The
4G module is magnetic
and can be mounted
to the near cabinet.
4G Module
Installing Mounting Ears
Installing Guide Rails
install four floating nuts.
Typical Rack-mounted Scenario
Connect cables to the lower
UPS and then to the upper
UPS.
•
The installation of the 6 kVA UPS is similar to that of the
10 kVA UPS. This document uses the 6 kVA UPS as an
example. Perform operations based on the actual
situation.
•
A UPS supports a maximum of eight lithium batteries in
parallel.
•
It is recommended that the BBB box be installed behind
the lithium batteries.
•
If four groups of batteries are installed in the rack-
mounted mode, reserve 1 U space between each two
groups of lithium batteries for battery cables.
•
You are advised to reserve 1 U space between UPSs, 1 U
space between the UPS and lithium battery, and 1 U space
above the UPS.
The following uses two 6 kVA UPSs and
two lithium batteries in rack-mounted
mode without a junction box as an
example.
If the build-out resistor is not installed,
the communication between the UPS
and batteries will fail.
Securing the UPS and Lithium batteries.
Connect the COM port on
the UPS to the COM_IN
port on the lithium battery.