UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
2 Quick Introduction
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
21
2.4 Optional Components
UPS2000-G-3 kVA cannot support parallel system.
For UPS2000-G-10 kVA/15 kVA/20 kVA, if the AC input and AC output uses two live
wires, PDC-0038V4ACIOA, PDC-0091V2ACIOA, and PDC-0038V4ACIOA-V2 cannot
be used.
Table 2-2
Optional components
Component Model
Function
Remarks
Parallel cable
DB15M, CC8P0.48B(S),
DB15F
Connect UPSs in
parallel for
UPS2000-G-6 kVA/10
kVA/15 kVA/20 kVA.
A parallel cable
is 1.5 meters
long.
Battery
temperature
sensor
TE820E10B/W103-B02-L1
Measures the ambient
temperature of the
external power module
and battery pack.
The temperature
ranges from
–40ºC to +80ºC.
The standard
cable is 2 meters
long. To
increase the
length, install a
magnetic ring at
the sensor plug.
Ambient
temperature
and humidity
sensor
WS302M2A-5
ENR1DETA MODULE
Measures the UPS
ambient temperature
and humidity.
The ambient
temperature
ranges from
0–50º
C. The
ambient
humidity ranges
from to
0%–100% RH.
It is used
together with a
Simple Network
Management
Protocol
(SNMP) card.
SNMP card
RMS-SNMP01A
Monitors the UPS and
the ambient
temperatures and
humidity (if required)
and allows for Ethernet
networking.
N/A
6 kVA output
isolation
DGL-6/0.22
Provides isolation
solutions for customer
The output
isolation