UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
9 Technical Specifications
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
101
Item
3 kVA
6 kVA
10 kVA
15 kVA
20 kVA
Dynamic voltage
tolerance
±5%
Output voltage
unbalance
N/A
±1% (balanced load)
±3% (unbalanced
load)
Average
frequency
tracking rate
0.5–2 Hz/s (single UPS) or 0.5–1 Hz/s (parallel system)
Power segment
(only in single
UPS mode)
If overloaded, the UPS disconnects from secondary loads and
checks whether it is still overloaded.
In battery mode, the UPS disconnects from secondary loads if the
battery voltage is less than the specified value.
In battery mode, the UPS disconnects from secondary loads if the
discharge time is more than the specified value.
9.6 Battery Specifications
Table 9-6
Battery specifications
Item
3 kVA
6 kVA
10 kVA
15 kVA
20 kVA
Rated battery
voltage
240 V DC
±240 V DC
Number of
batteries
16–20, each 12 V DC. If the smaller
value between the numbers of batteries,
N
, is less than 20, the battery power is
derated to
N
/20.
16–20, respectively in the
positive and negative battery
strings. The rated number is
20. If the smaller value
between the numbers of
batteries in the positive and
negative battery strings,
N
, is
less than 20, the battery
power is derated to
N
/20.
Battery string
sharing in a
parallel system
Disabled
Disabled
Disabled
Enabled
Enabled
Leakage current
≤ 500 μA
Depth of
discharge (DOD)
protection
The discharge time exceeds 16 hours (configurable on the LCD).
The single-battery voltage drops below 10.8 V in normal mode.
Backup time
> 4 minutes (at full rated load),