UPS2000-G-(3 kVA-20 kVA)-V2
User Manual (Two Live Wires)
9 Technical Specifications
Issue 07 (2019-12-19)
Copyright © Huawei Technologies Co., Ltd.
99
Item
3 kVA
6 kVA
10 kVA
15 kVA
20 kVA
to
40%–10
0%.)
%.)
138–485 V
AC,
three-phase
(When the
voltage is
138–305 V
AC, the load
power is
linearly
derated to
40%–100%.)
138–485 V
AC,
three-phase
(When the
voltage is
138–305 V
AC, the load
power is
linearly
derated to
40%–100%.)
Input power
factor (100%
load)
> 0.99
> 0.99
> 0.99
(single-phase
input)
> 0.95
(three-phase
input)
> 0.99
> 0.99
No-load loss
< 54 W
< 54 W
< 90 W
< 180 W
Double-power
input
Disabled
Disabled
Disabled
Enabled
Enabled
Startup voltage
120–280 V AC
Diesel
generator input
capacity
Minimum 1.5 times the UPS rated capacity
9.4 Bypass Input Electrical Specifications
Table 9-4
Bypass input electrical specifications
Item
3 kVA
6 kVA
10 kVA
15 kVA
20 kVA
Bypass voltage
Upper threshold: 10%/15%/20%/25%/30%@208 V AC
Upper threshold: 10%/15%/20%/25%@220 V AC
Upper threshold: 10%/15%/20%@230 V AC
Upper threshold: 10%/15%@240 V AC
Lower threshold: 10%/20%/30%/40%/50%/60%
Bypass
frequency
tolerance
Maximum ±6 Hz (configurable on the LCD)
Bypass overload
capability
Load < 125%: continuous in bypass mode