6 kVA/10 kVA Professional Version with
Long Backup Time
3
Installing Battery Cables (Only for UPS with Long Backup Time)
The battery cable connection method for a single UPS and a parallel system is the same. For
details, see page 5.
The UPS2000-A does not support battery string sharing.
4
Installing Parallel Communications Cables
UG10000083
PORT1
PORT2
PORT1
PORT2
UPS 2
UPS 1
This section describes the cable connection method for a 1+1 parallel system. Refer to this
method to connect the cables in other scenarios.
UPS2000-A-6KTTL-P
M4 (12 PCS)
1.4 N•m
UPS2000-A-10KTTL-P
M5 (12 PCS)
2.8 N•m
UPS 1
UPS 2
External power
distribution
(provide by the
customer)
Mains
AC
load
(1) AC input circuit breaker of UPS 1
(2) AC input circuit breaker of UPS 2
(3) AC output circuit breaker of UPS 1
(4) AC output circuit breaker of UPS 2
(5) General AC input circuit breaker of
the parallel system
(6) General AC output circuit breaker
of the parallel system