TP48200A-DT19C1, TP48200A-DT19C2,
TP48200A-HT19C1 and TP48200A-HT19C2 Telecom
Power
User Manual
3 Components
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
32
Pin
Signal
Description
4
RX+
Receives data over RS485.
5
RX-
3
RX232
Receives data over RS232.
7
TX232
Transmits data over RS232.
6
PGND
Connects to the ground.
8
NA
–
3.5 UIM02C
Panel
The user interface module (UIM02C) supports eight dry contact outputs, six dry contact
inputs, and seven sensor ports (including one ambient temperature and humidity input, one
water sensor input, two ambient temperature inputs, one door status sensor input, one smoke
sensor input, and one battery temperature input).
Figure 3-11
UIM02C panel
Ports
Table 3-7
UIM02C ports
Port Type
Silk Screen
Description
Sensor ports
TEM-HUM
Ambient temperature and humidity sensor
WATER
Water sensor
TEMP1
Ambient temperature sensor 1
TEMP2
Ambient temperature sensor 2
GATE
Door status sensor
SMOKE
Smoke sensor
BTEMP
Battery temperature sensor