SUN2000L-(2KTL-5KTL)
User Manual
7 Operations on the Local FusionHome App
Issue 02 (2017-12-12)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
95
Parameter
Description
Value Range
Level-1 UV protection
threshold (V)
Specifies the level-1
undervoltage protection
threshold.
[0.15xVn, 1xVn]
Level-1 UV protection
duration (ms)
Specifies the level-1
undervoltage protection
duration.
[50, 7200000]
Level-2 UV protection
threshold (V)
Specifies the level-2
undervoltage protection
threshold.
[0.15xVn, 1xVn]
Level-2 UV protection
duration (ms)
Specifies the level-2
undervoltage protection
duration.
[50, 7200000]
Level-1 OF protection
threshold (Hz)
Specifies the level-1
overfrequency protection
threshold.
[1xFn, 1.15xFn]
Level-1 OF protection
duration (ms)
Specifies the level-1
overfrequency protection
duration.
[50, 7200000]
Level-2 OF protection
threshold (Hz)
Specifies the level-2
overfrequency protection
threshold.
[1xFn, 1.15xFn]
Level-2 OF protection
duration (ms)
Specifies the level-2
overfrequency protection
duration.
[50, 7200000]
Level-1 UF protection
threshold (Hz)
Specifies the level-1
underfrequency protection
threshold.
[0.85xFn, 1xFn]
Level-1 UF protection
duration (ms)
Specifies the level-1
underfrequency protection
duration.
[50, 7200000]
Level-2 UF protection
threshold (Hz)
Specifies the level-2
underfrequency protection
threshold.
[0.85xFn, 1xFn]
Level-2 UF protection
duration (ms)
Specifies the level-2
underfrequency protection
duration.
[50, 7200000]
7.4.5.3 Feature Parameters
To set feature parameters, choose
Grid-connect config
>
Expert
>
Feature parameters
from the
Operation console
screen