background image

0

HUAWEI TECHNOLOGIES CO., LTD.

SUN2000-(25KTL, 30KTL)-US

Quick Installation Guide

Issue: 01
Part Number: 31507215
Date: 2016-06-15

Содержание SUN2000-25KTL-US

Страница 1: ...0 HUAWEI TECHNOLOGIES CO LTD SUN2000 25KTL 30KTL US Quick Installation Guide Issue 01 Part Number 31507215 Date 2016 06 15 ...

Страница 2: ...nsulated tools when installing the device For personal safety wear insulation gloves and protective shoes 6 When installing devices or connecting cables use appropriate tools and take necessary protective measures to avoid damaging devices during operation 7 The device warranty will not cover the following conditions The warranty label is removed The device is damaged caused by violation of the st...

Страница 3: ... with a back tilt of no more than 15 degrees for optimal heat dissipation conditions Installation dimensions Chassis dimensions Determining the Installation Mode 2 2 Installed on a Common Support Vertical Back tilt Upside down Front tilt Horizontal Installed on a Wall Vertical Back tilt Upside down Front tilt Horizontal NOTE 2 ...

Страница 4: ...Support Installed on a Common Support Back tilt Upside down Front tilt Horizontal 1 Determine the hole positions on the support based on rear panel dimensions 2 Drill holes 4 Mount the inverter on the rear panel 3 Secure the rear panel M12 3 PCS 45 N m ...

Страница 5: ...en hexagon bolts The anti theft lock is prepared by the customer Installed on a Wall 1 Determine the positions for drilling holes on the wall according to the rear panel dimensions 2 Drill holes and install expansion sleeves for expansion bolts NOTE ...

Страница 6: ...ilted support Front view 1 The hole dimensions of the bottom auxiliary tightening point in the top view are OB 13 mm x 8 mm OB 0 51 in x 0 31 in 2 The hole dimensions of the tightening point for the tilted support mounting kit in the front view are OB 32 mm x 12 mm OB 1 26 in x 0 47 in 3 The auxiliary tightening point is 5 mm 0 20 in away from the lower tightening point for the tilted support moun...

Страница 7: ... Installing Ground Cables 3 1 The hex key is stored in the fitting bag bound to the chassis base 1 Remove the two screws from the maintenance compartment door using a hex key and set them aside Electrical connections must meet local installation regulatory requirements 1 Do not leave unused screws in the chassis 2 Do not open the host panel of the inverter 3 Before opening the maintenance compartm...

Страница 8: ... cover and set it aside Ground Point Meaning Ground Point Screw Model Connection 1 PV side ground points M4 Connect either of the two ground points for PV side grounding 2 M6 3 Protection ground points M6 Connect either of the two ground points for protective grounding 4 4 Install ground cables ...

Страница 9: ...rding to the local and national regulations and installation specifications 2 UL1015 copper core cables that can withstand 105 C 221 F are recommended 3 It is recommended that the AC output cable be routed through a pipe for protection 4 The table lists only the recommended cable specifications For more information about cable specifications see the SUN2000 25KTL 30KTL US User Manual Cable Type Ca...

Страница 10: ...r wire output Three phase three wire output Adjust the sequence of installing AC output power cables based on site requirements Positive and negative metal terminals Negative metal terminal male Positive metal terminal female Number of Inputs SUN2000 25KTL 30KTL US 1 Connects to any one route 2 Connects to routes 1 and 3 3 Connects to routes 1 3 and 5 4 Connects to routes 1 2 3 and 5 5 Connects to...

Страница 11: ...the PV string voltage reduces to the safety range Then turn off the DC switch remove the positive and negative connectors and rectify the connection 5 The damage caused by reverse connection of the DC input power cable is beyond the warranty scope Ensure that the PV string is well insulated to the ground Before inserting the positive and negative connectors respectively into the positive and negat...

Страница 12: ...ing RS485 Communications Cables 3 5 NOTE 1 If RS485 is used connect the RS485 communications cable If PLC is used do not connect the communications cable 2 The RS485 communications cable can connect to either a terminal block or an RJ45 network port Use one connection mode in practice Connecting to the terminal block is recommended 3 If the RS485 communications cable is required you are advised to...

Страница 13: ...nect to RS485A and RS485B of the following inverter respectively 4 Secure the cable routing pipe NOTICE 12 1 Prepare an RS485 connector The figure shows the connector when the surface without the fastener faces upwards The following table lists the cable No color and pin definition You are advised to use a CAT 5E outdoor shielded network cable with a diameter less than 9 mm 0 35 in and internal re...

Страница 14: ...t circuit Yes No 5 AC output power cables are connected correctly and securely with no open circuit or short circuit Yes No 6 The DC input voltage is not higher than 1000 V and meets the local voltage range requirements Yes No 7 DC input power cables are connected correctly and securely with no open circuit or short circuit Yes No 8 RS485 communications cables are connected correctly and securely ...

Страница 15: ...ion Off The inverter has not received data over RS485 PLC communication for 10 seconds Alarm Maintenance indicator Alarm state Blinking red slowly on for 1s and then off for 4s The inverter has generated a warning Blinking red fast on for 0 5s and then off for 0 5s The inverter has generated a minor alarm Steady red The inverter has generated a major alarm Local maintenance state Blinking green sl...

Страница 16: ...p only over a USB data cable 3 Mobile operating system Android 4 0 or later 4 Access the Huawei app store http appstore huawei com or Google Play https play google com search for SUN2000 and download the SUN2000 APP software package 5 The SUN2000 communicates with its mobile application through a USB cable connected over the USB port 6 This document uses the WebUIs of SUN2000APP V200R001C00 as an ...

Страница 17: ...s password is used only when the SUN2000 is connected to the app 2 The initial password for Common User Advanced User and Special User is 00000a Use the initial password to log in to the inverter for the first time and change the password immediately to ensure account security 3 During the login if an incorrect password is entered for five consecutive times the interval between two consecutive inv...

Страница 18: ... the Temperatures at the Joints Between DC terminals and Connectors Using a Point Test Thermometer 7 2 Appendix Power Grid Code Mapping Table The grid codes are subject to change and are for your reference only For more information refer to the channels provided on the following page No Power Grid Standard Code Country and Condition 1 IEEE 1547 MV480 US medium voltage power grid 2 IEEE 1547a MV480...

Страница 19: ...hnical support website http support huawei com Support Scan here for technical support carrier Huawei App Store Huawei Technologies Co Ltd Huawei Industrial Base Bantian Longgang Shenzhen 518129 People s Republic of China www huawei com WeChat Google Play Apple Store ...