Master/Slave
: When the SmartLogger connects to multiple EMIs, set one of them to
master mode
.
Synchronize Environment Data
: When
Synchronize Environment Data
is set to
Enable
, wind
speed and direction data will be sent to the inverter in a PV plant with the tracking system.
Set
Read Mode
based on the mode supported by the EMI.
If
Multiple read
is selected, set
Start address
and
End address
based on the acquired Modbus
signal address range on the EMI.
If the EMI can collect a certain signal, set
Signal address
for the signal to the corresponding register
address. If the EMI cannot collect a certain signal, set
Signal address
for the signal to
65535
.
If you use any other model of EMI, select
Other
from the drop-down list box and set the
EMI parameters.
Figure 7-27
EMI (3)
Correctly set the parameters in accordance with the Modbus parameters provided by the EMI vendor.
Otherwise, the EMI data cannot be correctly read.
Master/Slave
: When the SmartLogger connects to multiple EMIs, set one of them to
master mode
.
Synchronize Environment Data
: When
Synchronize Environment Data
is set to
Enable
, wind
speed and direction data will be sent to the inverter in a PV plant with the tracking system.
Set
Read Mode
based on the mode supported by the EMI.
If
Multiple read
is selected, set
Start address
and
End address
based on the acquired Modbus
signal address range on the EMI.
If the EMI can collect a certain signal, set
Signal address
for the signal to the corresponding register
address. If the EMI cannot collect a certain signal, set
Signal address
for the signal to
65535
.
Connection over the AI/PT Port
After the SmartLogger connects to the EMI, you need to add the device manually. For details,
see
Device Type
to
EMI
and
Connection mode
to
AI
.
Because of permission restriction, log in as
Advanced User
. Choose
Monitoring
>
EMI
>
EMI(AI)
>
Running Param.
and set EMI parameters.