8 Power Grid Scheduling
Issue 12 (2019-01-15)
Copyright © Huawei Technologies Co., Ltd.
268
control mode
to
Remote scheduling
after receiving a scheduling command from the
upstream NMS.
Figure 8-16
Remote scheduling
8.3.9 Power Factor Closed-Loop Control
Before setting the parameters for power factor closed-loop control, ensure that the power
meter is connected to the SmartLogger. For details, see
4.6 Connecting the SmartLogger to a
Set
Reactive power control mode
to
Pwr factor closed-loop control
.