module 0 : normal
module 1 : normal
----------------------------------------------------------------------------
DigitalID Name Alarm State|DigitalID Name Alarm State
0 - Normal | 1 Fan Normal
2 - Normal | 3 SPD Normal
4 - Normal | 5 - Normal
6 - Normal
----------------------------------------------------------------------------
huawei(config-if-power4830-2)#
quit
huawei(config)#
save
3.15.2.2 Configuring the Monitoring Through the H831PMU (Backup Power Using
the VRLA Battery)
The H831PMU is a power monitoring control module and it works with the PAIB power board
to monitor relevant information about the power system. In addition, the H831PMU can manage
a VRLA battery set. This topic provides the basic information about the H831PMU and describes
how to configure data associated with environment monitoring.
Context
The H831PMU requires an RS-485 serial port for data communication.
Procedure
Step 1
Run the
emu add
command to add an environment monitoring unit (EMU).
Step 2
Configure the battery management parameters.
Run the
power battery parameter
command to configure battery parameters, such as charging
current-limiting coefficient, timed equalized charging time, number of battery sets, and capacity
of the battery set.
Step 3
Configure the battery charging parameters.
Run the
power charge
command to configure the battery charging mode and the equalized
charging voltage or floating charging voltage to charge the battery.
Step 4
Run the
power off
command to configure the power supply load power-off and battery set power-
off parameters.
Step 5
Run the
power supply-parameter
command to configure the power distribution parameters.
Step 6
Run the
display power system parameter
command to query the configuration parameters of
the power system.
Step 7
Save the data.
Run the
quit
command to quit the H831PMU mode, and then run the
save
command to save the
data.
----End
Result
After the configuration is completed, the H831PMU works in the normal state and monitors
parameters set on the MA5616. When a monitored parameter is abnormal, the MA5616 reports
an alarm.
SmartAX MA5616 Multi-service Access Module
Configuration Guide
3 Basic Configuration
Issue 04 (2011-10-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
145