Item
Data
Remarks
User-defined alarm ID of
digital parameter 2: 6
When the fan unit is faulty, the device reports an
alarm.
The meanings of the alarm IDs are as follows:
1: AC voltage; 2: AC switch; 3: battery voltage;
4: battery fuse; 5: load fuse; 6: rectifier module;
7: DC power; 8: room door; 9: thief; 10: wiring ;
11: fan; 12: fire; 13: fog; 14: power supply; 15:
water; 16: diesel; 17: smell 18: air-condition; 19:
arrester; 20: DC voltage; 21 output switch; 22:
digital user-defined alarm
huawei(config)#
emu add 3 MINIESC 0 8 RS485 MiniESC
huawei(config)#
interface emu 3
huawei(config-if-miniesc-3)#
esc analog 0 alarm-upper-limit 54 alarm-lower-limit 6
Send command to environment monitor board ,please waiting for the ack
huawei(config-if-miniesc-3)#
Execute command successful
huawei(config-if-miniesc-3)#
esc analog 2 alarm-upper-limit 75 alarm-lower-limit
5 name humidity sensor-type 0:voltage analog-alarm 2 unit %RH
Send command to environment monitor board ,please waiting for the ack
huawei(config-if-miniesc-3)#
Execute command successful
huawei(config-if-miniesc-3)#
esc digital 1 available-level high-level
Send command to environment monitor board ,please waiting for the ack
huawei(config-if-miniesc-3)#
Execute command successful
huawei(config-if-miniesc-3)#
esc digital 2 available-level low-level
digital-alarm 11 name Fan
Send command to environment monitor board ,please waiting for the ack
huawei(config-if-miniesc-3)#
Execute command successful
huawei(config-if-miniesc-3)#
display esc environment info
EMU ID: 3 ESC environment state
---------------------------Analog environment info--------------------------
ID Name State Value AlmUpper AlmLower Unit
0 Temperature Normal 30.00 54 6 C
1 Input_-48V_0 Normal 54.00 60 45 Volt
2 Humidity Low -128.00 75 5 %RH
3 - Normal -128.00 127 -128 -
---------------------------Digital environment info-------------------------
ID Name State Value |ID Name State Value
0 Wiring Normal 1 |1 Door0 Alarm 0
2 Fan Normal 0 |3 - Normal 1
4 - Normal 1 |5 - Normal 1
6 - Normal 1 |7 - Normal 1
8 Fog Normal 1 |9 Water_Alarm Normal 1
----------------------------------------------------------------------------
huawei(config-if-miniesc-3)#
quit
huawei(config)#
save
3.15.2 Configuring Monitoring Through the Power System
This topic describes how to configure the Power4830 and H831PMU on the MA5616.
SmartAX MA5616 Multi-service Access Module
Configuration Guide
3 Basic Configuration
Issue 04 (2011-10-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
138