SmartACU2000B smart array controller
User Manual (with PID modules, 800 V AC)
A Configuring the DI7 and DI8 Ports
Issue 05 (2019-01-20)
Copyright © Huawei Technologies Co., Ltd.
106
A
Configuring the DI7 and DI8 Ports
Procedure
Step 1
Enter
https://XX.XX.XX.XX
in the address box of the browser to enter the WebUI login
page. Because of permission restriction, log in as
Special User
.
XX.XX.XX.XX indicates the IP address for the SmartLogger2000. The default IP address is
192.168.0.10.
If web pages cannot be opened, specify security settings for the browser. For details, see the
appropriate
SmartLogger2000 User Manual
.
The initial password is
Changeme
.
Use the initial password upon first power-on and change it immediately after login. To ensure
account security, change the password periodically and keep the new password in mind. Not
changing the initial password may cause password disclosure. A password left unchanged for a long
period of time may be stolen or cracked. If a password is lost, devices cannot be accessed. In these
cases, the user is liable for any loss caused to the PV plant.
Step 2
Choose
Settings
>
DI
to enter the page for configuring the DI7 and DI8 ports.
Table A-1
DI7 port parameter settings
Parameter
Value
Parameter
Value
Activation Status
Activated
Alarm Severity
Major
Alarm Generation
Enable
Alarm Name
24V power failure
Table A-2
DI8 port parameter settings
Parameter
Value
Parameter
Value
Activation Status
Activated
Alarm Severity
Major
Alarm Generation
Enable
Alarm Name
AC SPD fault
----End