PowerCube 5000
User Manual (SmartLi 100Ah)
3 Installation
Issue 02 (2020-03-17)
Copyright © Huawei Technologies Co., Ltd.
74
Figure 3-23
Installing a water sensor
Step 3
Check the function of the water sensor.
Table 3-5
Function check
Check Method
Normal Connection
Status
Alarm Clearance Method
Immerse the water sensor
into water.
A water alarm is displayed
on the active alarm page of
the monitoring system.
Wipe dry the water sensor.
The alarm disappears
automatically.
----End
3.6 (Optional) Installing a Combiner Box
Prerequisites
A combiner box is provided.
Procedure
Step 1
Determine the position for installing a combiner box on the wall based on the hole dimensions
diagram.