
PowerCube 5000 (SUN2000-150KTL-S0)
Installation Guide
9 Power-on and Commissioning
Issue 03 (2020-04-10)
Copyright © Huawei Technologies Co., Ltd.
78
Table 9-11
Setting NetEco configuration parameters
Path
Parameters
Default Value
Setting
System Info
>
Settings
>
Communication
NetEco Primary IP
192.168.000.010
Set this parameter
based on the address
assigned by the
network
administrator.
NetEco Port
Number
31220
Set based on site
requirements.
NOTE
Configurable range:
1–65525
Step 7
(Optional) Set the parameters of the transformer surge protection and high temperature
alarms.
The parameters need to be set on the MDU of the slave cabinet only in the parallel system scenario.
Path
Parameters
Setting
System Info
>
Settings
>
Basic Param.
Transformer Cab SPD Fault
Condition
Close
NOTE
The transformer surge
protection alarm is shielded.
System Info
>
Settings
>
Basic Param.
DIN5 Reuse
None
NOTE
The transformer high
temperature alarm is shielded.
----End
9.3 Connecting the Load Power Supply
Procedure
Step 1
Turn the isolation switch in the isolation transformer to ON.