Locati
on
Display Name Addr
ess
DIP Switch Sequence No.
1
2
3
4
5
6
Cold aisle 2
temp/humid
12
OFF
OFF
ON
ON
OFF
OFF
Cold aisle 3
temp/humid
13
ON
OFF
ON
ON
OFF
OFF
Cold aisle 4
temp/humid
14
OFF
ON
ON
ON
OFF
OFF
Cold aisle 5
temp/humid
15
ON
ON
ON
ON
OFF
OFF
Hot
aisle
Hot aisle 1
temp/humid
21
ON
OFF
ON
OFF
ON
OFF
Hot aisle 2
temp/humid
22
OFF
ON
ON
OFF
ON
OFF
Hot aisle 3
temp/humid
23
ON
ON
ON
OFF
ON
OFF
Hot aisle 4
temp/humid
24
OFF
OFF
OFF
ON
ON
OFF
Hot aisle 5
temp/humid
25
ON
OFF
OFF
ON
ON
OFF
NO TICE
● The default addresses of T/H sensors purchased from Huawei are 1.
● Keep the last RS485_R toggle switch at OFF.
● After the addresses are set, power on the device. On the display's home screen,
choose Settings > System Settings > T/H Sensor, and set the sensors in the
aisles corresponding to the addresses to Enable. Otherwise, the sensors will not
work.
----End
3.13 Removing the Transport Fasteners and Protective
Covers
Procedure
Step 1 Open the No. 2nd maintenance door. Loosen the three bolts on the compressor
transport fasteners using a 13# solid wrench.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
3 Installation Guide
Issue 06 (2020-08-19)
Copyright © Huawei Technologies Co., Ltd.
69