Figure 4-24 System power limit set successfully
----End
4.5 Startup
Context
Tap the Start or Shutdown buttons on the home screen to start or shut down the
smart cooling product.
●
If a power failure occurs and the smart cooling product is powered on again,
the smart cooling product automatically restores to the original state (start or
shutdown) before the power failure.
●
The hardware port for controlling the status of the remote dry contact or
On/Off status on remote is reserved on the ACC. The status of the remote dry
contact and On/Off status on remote is on by default.
●
The operations that start the smart cooling product successfully by the display
button or by element management system (EMS) is effective only when the
remote dry contact or On/Off status on remote is on the status of on.
Prerequisites
Download the Service Expert app from Huawei app store and runs on Android.
Apply for permission after downloading the app.
Step 1 Tap Start on the home screen of the ACC.
●
If the screen shown in
is displayed, tap Yes. Indicating initial
startup, perform
for initial startup verification.
NetCol8000-E220 Modular Indirect Evaporative
Cooling System
User Manual
4 Power-on and Commissioning
Issue 06 (2020-08-19)