NO TE
● Connect the COM/FE port on the main control module of the last unit in each group to
the RS485 port on the host.
● Customers can purchase an ECC and NetEco as the monitoring system.
Figure 3-44 Connecting communications cables
----End
3.6.4.2.2 CAN Te FE Monitoring
Step 1 Connect teamwork and monitoring communications cables.
Networking
CAN Teamwork
FE Monitoring
Protocol
CAN
Modbus-TCP/SNMP
Description
One teamwork network
supports a maximum of 32
units. On the Teamwork
Settings screen of the display
modules of the first and last
units, set Enable teamwork
CAN resistor to Yes.
-
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
3 Installation
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
70