inlet to facilitate maintenance. The water pressure should be in the range of
100–700 kPa. The water should be free from large particles.
3.5.6 (Optional) Leakage Test with Nitrogen
Context
Install a reducing valve at the outlet of the nitrogen cylinder. The outlet pressure
of the reducing valve must be not more than 0.8 MPa.
Procedure
Step 1 Rotate the chilled water valve to the maximum openness (100%).
Step 2 Check that the needle valves and exhaust valves on the pipeline are closed.
Step 3 Connect the reducing valve and nitrogen cylinder to the following needle valve,
inject 0.8 MPa (when the pressure is stable) nitrogen, and leave them for 24
hours.
Figure 3-31 Upflow
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
3 Installation
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
59