3. Install cables and secure them using cable ties.
Step 7 Power on the device, choose Maint > Wizard Startup on the home screen, and
commission the water valve actuator to check that it works properly before you
exit.
Step 8 On the home screen, choose Maint > Performance Maint to enter the
Performance Maint screen and clear the runtime of the chilled water valve.
----End
6.4.8 Replacing a PSU
Context
NO TICE
● This section describes how to replace a PSU and provides a reference for
replacing a main control module.
● The new PSU must be installed in the same slot of the faulty PSU. Otherwise,
the smart cooling product may fail to work properly.
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
NO TICE
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Open the front door and push the latch on the PSU downwards, as shown by (1)
in
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
6 Maintenance
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
184