When the electric heater is turned on, the indoor fans will turn on automatically.
When the electrode humidifier is turned on, the indoor fans and inlet water solenoid valve
will start automatically.
When the input value of the indoor fan is less than the minimum speed, the indoor fan will
run at the minimum speed.
Step 3
Check that the indoor fans run properly, and no alarm generates.
Step 4
Choose
Maint
>
Diagnostic Mode
>
Exit
or tap
to exit the diagnostic mode.
----End
7.1.16 Restoring Factory Settings
Context
If you have forgotten the password or need to delete system information, you can restore
factory settings using SW button on the main control module.
If you restore factory settings, all system data will be restored to the state before delivery,
including login passwords, operation logs, parameter configurations, alarms, and
performance statistics. Perform this operation with caution as it may affect other users.
To ensure information security and prevent malicious password reset, you must keep the
cabinet keys securely. If any abnormal operation is found, check the information in the
equipment room access control system and monitoring system.
Procedure
Step 1
Tap
Shutdown
on the screen and wait for the system to shut down.
Step 2
Press the SW button on the main control module for at least 10s.
button on the main control module.