NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
270
Figure 6-35
Electric heater position
Step 6
Install and secure the new electric heater by performing
to
. Install the fan
maintenance baffle and close the front door.
Step 7
Power on the device. Tap
Start
on the home screen, and choose
Maint
>
Diagnostic Mode
>
Enter
. Then start the electric heater and check that the heater operates properly. Then exit
from the diagnostic mode.
Step 8
On the home screen, choose
Maint
>
Performance Maint
to enter the performance
maintenance screen and clear the runtime of the electric heater.
----End
6.7.11 Replacing the Low Liquid Level Detector
Context
Tool: Phillips screwdriver
Procedure
Step 1
Tap
Shutdown
on the LCD home screen.
Step 2
Open the front door and turn off the general switch. For a device that has two power inputs,
turn off the active power switch QF1 and standby power switch QF2.
Step 3
Disconnect the interconnection terminal of the low liquid level detector.
Step 4
Remove the low liquid level detector fastener.
For upflow units: Remove the butterfly nuts on the low liquid level detector fastener and
pull out the fastener upwards.